SIEMENS
SINAMICS G180
Configuring instructions
Cable cross-sections and connections
5/9
Siemens D 18.1 · 2014
5
■
Overview
(continued)
Type
rating
Converter
Converter type
Line connection
(standard)
Line connection
with main
switch or circuit breaker
(Options:
S01
,
S02
,
S03
,
S04
,
S06
,
S08
,
S09
,
S11
,
S12
,
S21
,
S22
,
S23
,
S24
,
S41
)
Motor connection
SINAMICS G180
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
min.
max.
min.
max.
min.
max.
kW
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
SINAMICS G180 cabinet system 400 V 6-pulse (230 to 500 V 3 AC TN/TT system, 50 to 60 Hz)
2.2
6SE0140-1.C15-5.A7
2X.A-8740.-002
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
3
6SE0140-1.C17-0.A7
2X.A-8740.-003
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
4
6SE0140-1.C21-0.A7
2X.A-8740.-004
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
5.5
6SE0140-1.C21-3.A7
2X.A-8740.-005
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
7.5
6SE0140-1.C21-8.A7
2X.A-8740.-007
4
16
Terminal
4
16
Terminal
4
16
Terminal
11
6SE0140-1.C22-5.A7
2X.A-8740.-011
4
16
Terminal
4
16
Terminal
4
16
Terminal
15
6SE0140-1.C23-7.A7
2X.A-8740.-015
0.75
35
Terminal
0.75
35
Terminal
0.75
35
Terminal
22
6SE0140-1.C24-8.A7
2X.A-8740.-022
0.75
35
Terminal
0.75
35
Terminal
0.75
35
Terminal
30
6SE0140-1.C25-8.A7
2X.A-8740.-030
0.75
35
Terminal
0.75
35
Terminal
0.75
35
Terminal
37
6SE0140-1.C27-8.A7
2X.A-8740.-037
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
45
6SE0140-1.C28-8.A7
2X.A-8740.-045
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
55
6SE0140-1.C31-1.A7
2X.A-8740.-055
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
75
6SE0140-1.C31-5.A7
2X.A-8740.-075
2 × 6
2 × 300
1 × M10
2 × 2.5
2 × 150
1 × M6
2 × 6
2 × 300
1 × M10
90
6SE0140-1.C31-8.A7
2X.A-8740.-090
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
110
6SE0140-1.C32-1.A7
2X.A-8740.-110
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
132
6SE0140-1.C32-5.A7
2X.A-8740.-132
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
160
6SE0140-1.C33-0.A7
2X.A-8740.-160
2 × 6
2 × 300
1 × M10
2 × 6
2 × 300
1 × M10
2 × 6
2 × 300
1 × M10
SINAMICS G180 cabinet systems 500 V 6-pulse (230 to 500 V 3 AC IT system, 50 to 60 Hz)
2.2
6SE0140-1.D14-5.A7
2X.A-8750.-002
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
3
6SE0140-1.D15-5.A7
2X.A-8750.-003
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
4
6SE0140-1.D17-0.A7
2X.A-8750.-004
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
5.5
6SE0140-1.D21-0.A7
2X.A-8750.-005
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
7.5
6SE0140-1.D21-3.A7
2X.A-8750.-007
0.5
10
Terminal
0.5
10
Terminal
0.5
10
Terminal
11
6SE0140-1.D21-8.A7
2X.A-8750.-011
4
16
Terminal
4
16
Terminal
4
16
Terminal
15
6SE0140-1.D22-5.A7
2X.A-8750.-015
4
16
Terminal
4
16
Terminal
4
16
Terminal
22
6SE0140-1.D23-7.A7
2X.A-8750.-022
0.75
35
Terminal
0.75
35
Terminal
0.75
35
Terminal
30
6SE0140-1.D24-8.A7
2X.A-8750.-030
0.75
35
Terminal
0.75
35
Terminal
0.75
35
Terminal
37
6SE0140-1.D25-8.A7
2X.A-8750.-037
0.75
35
Terminal
0.75
35
Terminal
0.75
35
Terminal
45
6SE0140-1.D27-8.A7
2X.A-8750.-045
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
55
6SE0140-1.D28-8.A7
2X.A-8750.-055
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
75
6SE0140-1.D31-1.A7
2X.A-8750.-075
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
90
6SE0140-1.D31-5.A7
2X.A-8750.-090
2 × 6
2 × 300
1 × M10
2 × 2.5
2 × 150
1 × M6
2 × 6
2 × 300
1 × M10
110
6SE0140-1.D31-8.A7
2X.A-8750.-110
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
132
6SE0140-1.D32-1.A7
2X.A-8750.-132
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
160
6SE0140-1.D32-5.A7
2X.A-8750.-160
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
200
6SE0140-1.D33-0.A7
2X.A-8750.-200
2 × 6
2 × 300
1 × M10
2 × 6
2 × 300
1 × M10
2 × 6
2 × 300
1 × M10
SINAMICS G180 cabinet systems 690 V 6-pulse (230 to 600
1)
/690 V 3 AC TN/TT or IT system, 50 to 60 Hz)
7.5
6SE0140-1. .21-0.A7
2X.A-8769.-007
4
16
Terminal
4
16
Terminal
4
16
Terminal
11
6SE0140-1. .21-3.A7
2X.A-8769.-011
4
16
Terminal
4
16
Terminal
4
16
Terminal
15
6SE0140-1. .21-8.A7
2X.A-8769.-015
4
16
Terminal
4
16
Terminal
4
16
Terminal
22
6SE0140-1. .22-5.A7
2X.A-8769.-022
4
16
Terminal
4
16
Terminal
4
16
Terminal
30
6SE0140-1. .23-4.A7
2X.A-8769.-030
2 × 6
2 × 300
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
37
6SE0140-1. .24-2.A7
2X.A-8769.-037
2 × 6
2 × 300
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
45
6SE0140-1. .25-0.A7
2X.A-8769.-045
2 × 6
2 × 300
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
55
6SE0140-1. .25-8.A7
2X.A-8769.-055
2 × 6
2 × 300
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
75
6SE0140-1. .28-0.A7
2X.A-8769.-075
2 × 6
2 × 300
1 × M10
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
90
6SE0140-1. .31-0.A7
2X.A-8769.-090
2 × 6
2 × 300
1 × M10
2 × 2.5
2 × 150
1 × M6
2 × 6
2 × 300
1 × M10
110
6SE0140-1. .31-2.A7
2X.A-8769.-110
2 × 6
2 × 300
1 × M10
2 × 2.5
2 × 150
1 × M6
2 × 6
2 × 300
1 × M10
132
6SE0140-1. .31-4.A7
2X.A-8769.-132
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
160
6SE0140-1. .31-7.A7
2X.A-8769.-160
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
200
6SE0140-1. .32-1.A7
2X.A-8769.-200
2 × 6
2 × 300
1 × M10
2 × 6
2 × 185
1 × M10
2 × 6
2 × 300
1 × M10
1)
With an NRTL unit ("U" in 14th position of article number), the voltage range ends at max. 600 V, otherwise at 690 V.