SIEMENS
SINAMICS G180
SINAMICS G180 compact units and SINAMICS G180 cabinet systems
SINAMICS G180 compact units
2/3
Siemens D 18.1 · 2014
2
■
Technical data
(continued)
General technical data
Deviations from the specified classes are underlined
.
Electrical data
Line voltages
Type of supply system
Power ranges
230 ...
400
... 500 V 3 AC, -15/+10 %
TN/TT system
2.2 ... 160 kW (at 400 V)
230 ...
500
V 3 AC, -15/+10 %
IT system
2.2 ... 200 kW (at 500 V)
230 ...
690
V 3 AC, -15/+10 %
TN/TT or IT system
7.5 ... 200 kW (at 690 V)
Line frequency
47 ... 63 Hz
Output frequency
0 ... 250 Hz
Voltage rise in motor
Typ. 500 ... 1000 V/μs, but < 1500 V/μs
Typical line harmonics (
I
) in % of
fundamental mode for the
5/7/11/13/17/19/23/25 harmonics max.
38/18/8/7/5/4/3/2
Typical line harmonics (
I
) in % of
fundamental mode for the
5/7/11/13/17/19/23/25 harmonics max.
with LHF filter
1.4/3.6/2.4/1.7/1.0/0.6/0.8/0.4
Pulse number
6
Overvoltage category
III to EN 61800-5-1
Short Circuit Current Rating (SCCR)
according to UL508C (up to 600 V), in
conjunction with the specified fuses or
circuit breakers
60 kA
Control method
• For motors: Field-oriented control (FOC) with sensor and approval for explosion-proof motors as well as
vector control (SVC) with/without sensor (speed, process
speed (n)
, torque, hoist
1)
, line
synchronization
1)
)
• Motor-independent control of current or voltage (current, process
current (I)
, voltage, process
voltage (U)
)
Fixed speeds
3 fixed speeds + 1 minimum speed, parameterizable
Skipped speed ranges
2, parameterizable
Setpoint resolution
13 bits digital with
n
/
f
setpoint, 12 bits digital with
U
/
I
torque setpoint, 9 bits + sign analog
Braking operation
The oversaturation control system makes it possible to generate a braking torque of up to 50 % at low to
mid-range speeds, and of up to 10 % at high speeds. If a higher braking torque is required, an optionally
available braking module with appropriate braking resistor must be installed.
Mechanical data
Degree of protection
IP20, optionally IP21 provided by protective top cover (aluminum, unpainted)
Protection class
I acc. to EN 61800-5-1
Touch protection
EN 50274 / BGV A3
Type of cooling
Forced air cooling AF to EN 60146
Paint finish
RAL 9023 (R-Pearl Dark Grey)
Cable entry
From below
Ambient conditions
2)
Storage
3)
Transport
3)
Operation
Ambient temperature
-25 ... +70
°C
Class 1K4 acc. to EN 60721-3-1
-25 ... +70 °C
down to -40
°C for 24h
Class 2K3 acc. to EN 60721-3-2
Air: 0
... 40 °C/
–
Relative humidity
(condensation not permissible)
5
... 95
%
Class 1K3 acc. to EN 60721-3-1
5 ... 95 %
Class 2K3 acc. to EN 60721-3-2
5 ... 95
%
Class 3K3 acc. to EN 60721-3-3
Environmental class/harmful
chemical substances
Class 1C2 acc. to EN 60721-3-1
Class 2C2 acc. to EN 60721-3-2
Class 3C2 acc. to EN 60721-3-3
Organic/biological influences
Class 1B1 acc. to EN 60721-3-1
Class 2B1 acc. to EN 60721-3-2
Class 3B1 acc. to EN 60721-3-3
Pollution degree
2 acc. to EN 61800-5-1
Installation altitude
Up to 1000 m above sea level without derating, > 1000 m see derating table (in chapter Configuring instructions)
Mechanical stability
2)
Storage
3)
Transport
3)
Operation
Vibratory load
• Deflection
• Acceleration
1.5 mm at 5
... 9 Hz
5 m/s
2
at > 9 ... 200 Hz
Class 1M2 acc. to EN 60721-3-1
3.1
mm at 5
... 9 Hz
10 m/s
2
at > 9 ... 200 Hz
Class 2M2 acc. to EN 60721-3-2
0.075 mm at 10 … 58 Hz
10 m/s
2
at > 58 … 200 Hz
–
Shock load
• Acceleration
40 m/s
2
at 22 ms
Class 1M2 acc. to EN 60721-3-1
100 m/s
2
at 11 ms
Class 2M2 acc. to EN 60721-3-2
100 m/s
2
at 11 ms
Class 3M4 acc. to EN 60721-3-3
Compliance with standards
CE Label
Acc. to EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC
Radio interference suppression
Complies with EMC guidelines defined in EN 61800-3 thanks to line filter which is integrated as standard
(with grounded supply system):
• Category C2 for compact units in TN/TT system of the first environment (residential area),
category C1 available as an option
• Category C4 for compact units in IT system of the second environment (industrial area)
Approvals
TÜV NRTL US
2)
1)
On request
2)
Higher standards on request
3)
In transport packaging
© Siemens AG 2014