SIEMENS
SINAMICS G180
Option descriptions
Standard options
4/31
Siemens D 18.1 · 2014
4
■
Options
(continued)
H80, H81, H82, H83, H84, H85 and H86
Cabinet widths for cabinet systems with compact units
H90, H91, H92, H93 and H94
Additional cabinets for cabinet units
V61, V62 and V63
Ambient temperature for air-cooled converters
The maximum permissible coolant temperature is 40 °C for
air-cooled units. If operation is required with higher coolant
temperatures, derating is necessary.
V66, V67 and V68
Water inlet temperature for liquid-cooled converters
The maximum permissible water inlet temperature is between 28
and 35 °C depending on the converter type (see technical data
for maximum cooling water temperature). If operation is required
with higher coolant temperatures, derating is necessary.
V86, V87, V88 and V89
Installation altitude
At an installation altitude for the SINAMICS G180 of over 1000 m
above sea level, reduced cooling caused by the lower air
pressure and cosmic radiation means that the input voltage
must be reduced (see the section "Characteristic curves" under
"Configuring instructions"). Options
V86
to
V89
specify the in-
stallation altitude of the converter.
V70, V71, V72, V73, V74, V75, V76, V77, V78, V79, V80
and Y70
Line voltages
Options V70 to Y70 are used to select the line voltage.
These options mutually exclude each other.
Y13
Language of manual
Y13
Different languages for manual
The following languages are available for the manual:
• Bulgarian
• Czech
• German
• English
• Spanish
• French
• Dutch
• Polish
• Russian
• Norwegian
Note:
Other languages on request.
Option
Description
H80
Cabinet width: 406 mm
H81
Cabinet width: 606 mm
H82
Cabinet width: 806 mm
H83
Cabinet width: 1006 mm
H84
Cabinet width: 1206 mm
H85
Cabinet width: 1406 mm
H86
Cabinet width: 1606 mm
Option
Description
H90
Additional cabinet: 400 mm
H91
Additional cabinet: 600 mm
H92
Additional cabinet: 800 mm
H93
Additional cabinet: 1000 mm
H94
Additional cabinet: 1200 mm
Option
Description
V61
45 °C ambient temperature
(with corresponding derating)
V62
50 °C ambient temperature
(with corresponding derating)
V63
55 °C ambient temperature
(for compact units with corresponding derating)
Option
Description
V66
30 °C water inlet temperature
(with corresponding derating)
V67
35 °C water inlet temperature
(with corresponding derating)
V68
40 °C water inlet temperature
(with corresponding derating)
Option
Description
V86
Installation altitude max. 1500 m above sea level
(with corresponding derating)
V87
Installation altitude max. 2000 m above sea level
(with corresponding derating)
V88
Installation altitude max. 2500 m above sea level
(with corresponding derating)
V89
Installation altitude max. 3000 m above sea level
(with corresponding derating)
Option
Description
V70
Line voltage 380 V, 50 Hz
V71
Line voltage 400 V, 50 Hz
V72
Line voltage 415 V, 50 Hz
V73
Line voltage 500 V, 50 Hz
V74
Line voltage 660 V, 50 Hz
V75
Line voltage 690 V, 50 Hz
V76
Line voltage 440 V, 60 Hz
V77
Line voltage 460 V, 60 Hz
V78
Line voltage 480 V, 60 Hz
V79
Line voltage 600 V, 60 Hz
V80
Line voltage 660 V, 60 Hz
Y70
Special line voltage; please specify voltage