SIEMENS
SINAMICS G180
Option descriptions
Standard options
4/22
Siemens D 18.1 · 2014
4
■
Options
(continued)
L92
Pt100 evaluation unit for motor winding temperature,
integrated in control cabinet for monitoring 3 × Pt100 sensors;
plus an analog output 0 to 10 V or 0(4) to 20 mA connected to
terminals for the hottest winding temperature
L92
Pt100 Ziehl TR400
Pt100 evaluation unit for 3 × Pt100 sensors for 3 winding sensors
(1 reserve), installed in the control cabinet. With temperature
indication on the evaluation unit; alarm and trip message on the
converter display or integrated in the group warning or group
fault.
Also one analog output 0 to 10 V or 0(4) to 20 mA for the hottest
winding temperature for further processing, e.g. in the main
control system; applied to terminals.
Note:
Please specify alarm and trip limits in the order for motors that
are not included in the scope of supply.
L93
Pt100 evaluation unit for motor bearing temperature,
integrated in control cabinet for monitoring 2 × Pt100 sensors or
2 × KTY83/84 sensors; plus two analog outputs
0 to 10 V or 0(4) to 20 mA connected to terminals for
bearing temperature
Pt100 evaluation unit for 2 × Pt100 sensors or 2 × KTY83/84
sensors for motor bearing temperature, integrated in the control
cabinet. With temperature indication on the evaluation unit;
alarm and trip message on the converter display or integrated in
the group warning or group fault.
Also two analog outputs 0 to 10 V or 0(4) to 20 mA for the
bearing temperature for further processing, e.g. in the main
control system; applied to terminals.
Note:
Please specify alarm and trip limits in the order for motors that
are not included in the scope of supply.
L94
Pt100 evaluation unit for motor winding and
bearing temperatures, integrated in control cabinet for monitor-
ing 6 × Pt100 sensors; plus two analog outputs 0 to 10 V or 0(4)
to 20 mA connected to terminals for the hottest winding and
bearing temperatures
L94
Pt100 Ziehl TR600
Pt100 evaluation unit for 6 × Pt100 sensors for 3 winding sensors
and 2 bearing sensors (1 reserve), integrated in the control cab-
inet; temperature indication on evaluation unit; alarm and trip
message on converter display or integrated into the group warn-
ing or group fault.
Also one analog output 0 to 10 V or 0(4) to 20 mA for the hottest
winding temperature and one analog output 0 to 10 V or
0(4) to 20 mA for the hottest bearing temperature for further pro-
cessing, e.g. in the main control system; applied to terminals.
Note:
Please specify alarm and trip limits in the order for motors that
are not included in the scope of supply.
Y90
Pt100 evaluation unit for other temperature monitoring
functions, integrated in control cabinet for monitoring of 3 ×
Pt100 or 3 × KTY83/84 sensors
For image, see option
L90
Siemens 3RS1041-1GW50.
Pt100 evaluation unit for motor winding temperature, integrated
in control cabinet for 3 × Pt100/1000 or 3 × KTY83/84 sensors;
temperature indication on evaluation unit, alarm and trip mes-
sage on converter display or integrated into the group warning
or group fault.
Note:
Please specify alarm and trip limits or which temperatures
should be monitored in the order.
Y94
Pt100 evaluation unit for other temperature monitoring
functions, integrated in control cabinet for monitoring
6 × Pt100 sensors; plus two analog outputs
0 to 10 V or 0(4) to 20 mA connected to terminals
For image, see option
L94
Pt100 Ziehl TR600.
Pt100 evaluation unit for 6 × Pt100 sensors integrated in control
cabinet; temperature indication on evaluation unit; alarm and trip
message on converter display or integrated into the group
warning or group fault.
Also two analog outputs 0 to 10 V or 0(4) to 20 mA applied to
terminals.
© Siemens AG 2014