SIEMENS
SINAMICS G180
Option descriptions
Standard options
4/15
Siemens D 18.1 · 2014
4
■
Options
(continued)
L00 and L02
RFI suppression filter
Inadmissible option combinations
L00
and
L02
L00
RFI suppression filter Category C2 or C3 (Class A)
Option
L00
comprises an RFI suppression filter of Class A.
This fulfills the following requirements:
•
For compact units in a TN/TT system:
RFI suppression filter acc. to EN 55011 Class A and EMC
product standard EN 61800-3 Category C2
(environment 1, public network)
•
For cabinet units in a TN/TT system:
RFI suppression filter acc. to EN 55011 Class A and EMC
product standard EN 61800-3 Category C3
(environment 2, industrial area)
Note:
Option
L00
is only permitted to be installed for devices that are
intended for use in grounded networks, i.e. for 400 V devices
(only permitted to be used in grounded systems) and for 500 V
or 690 V devices that operate on a grounded line voltage.
For units in category C2 the following applies:
If not correctly installed and commissioned, this product can
cause radio frequency interference in residential areas. In this
case, it may be necessary for the operator of the unit to take
further interference suppression measures.
L02
RFI suppression filter EN 55011 Class B
Option
L02
comprises an RFI suppression filter of Class B.
This fulfills the following requirements for compact units:
RFI suppression filter acc. to EN 55011 Class B and EMC
product standard EN 61800-3 Category C1
(environment 1, residential area).
Note
:
Option
L02
is only permitted to be installed for devices that are
intended for use in grounded networks, i.e. for 400 V devices
(only permitted to be used in grounded systems) and for those
that operate on a grounded line voltage.
L03 and L04
Line Harmonics Filter
L03
/
L04
Example of a Line Harmonics Filter in the cabinet unit
L03
/
L04
Example of a Line Harmonics Filter in the converter cabinet
with compact unit
Inadmissible option combinations
L03
and
L04
L03
Line Harmonics Filter for 50 Hz line frequency
With option
L03
a Line Harmonics Filter for 50 Hz line frequency
will be installed in the control cabinet for reducing the line-side
harmonics or for compliance with IEEE 519. See the general
technical data.
Note:
Please ask your Siemens contact person for the exact cabinet
dimensions.
L04
Line Harmonics Filter for 60 Hz line frequency
With option
L04
a Line Harmonics Filter for 60 Hz line frequency
will be installed in the control cabinet for reducing the line-side
harmonics or for compliance with IEEE 519. See the general
technical data.
Note:
Please ask your Siemens contact person for the exact cabinet
dimensions.
RFI suppression filter
L00
L02
RFI suppression filter EN 55011 Class A
L00
–
RFI suppression filter EN 55011 Class B
L02
–
–
Options mutually exclude each other.
Line Harmonics Filter
L03
L04
Line Harmonics Filter for 50 Hz line frequency
L03
–
Line Harmonics Filter for 60 Hz line frequency
L04
–
–
Options mutually exclude each other.
© Siemens AG 2014