SIEMENS
SINAMICS G180
Option descriptions
Standard options
4/9
Siemens D 18.1 · 2014
4
■
Options
(continued)
G04
Peripheral board 3
G04
Peripheral board 3 in the compact unit
Option
G04
(peripheral board 3) provides in addition to standard
converter terminals:
•
2 analog outputs (AO) 4 to 20 mA/0 to 10 V
•
One digital input "Safe Torque Off" (STO, single-channel or
two-channel) acc. to EN ISO 13849-1, Cat. 3 or SIL 2
acc. to EN 61508
9 digital inputs (DI)
•
3 relay outputs (DO)
In addition, the relay outputs here are not only isolated from
the converter electronics but also from each other.
•
24 V / 300 mA power supply unit
SIL 2 (acc. to EN 61508) – STO (Safe Torque Off).
Safe Torque Off (STO) function implemented according to
SIL 2 to EN 61508.
The "Safe Torque Off" (STO) function has a redundant switch-off
path in the converter. The implementation is performed using
hardware. A relay in the power unit of the converter disconnects
the power supply of the IGBT driver. A second circuit, also via
hardware, produces a controller disable.
The "Safe Torque Off" input can be implemented with either one
or two channels. The board is coded for single-channel activa-
tion at the factory. If two-channel activation is required, please
specify this in the order. Digital input X2:24 is reserved for the
two-channel version.
Standard assignment of inputs/outputs
The table below provides an overview of the pre-assignment
function of interfaces in the pin assignments for the "Standard"
application.
NAMUR-compliant assignment of inputs/outputs
The table below provides an overview of the pre-assignment
function of interfaces in the pin assignments for the "NAMUR"
application.
Signal designation
Function
Internal digital input 19, 20
24 V DC; "Safe Torque Off"
acc. to EN ISO 13849-1,
Cat. 3; or SIL 2 acc. to EN 61508
Internal digital input 6, 7, 21, 22,
23, 24, 25, 26
Freely parameterizable
Internal PTC thermistor input 90,
91, 92, 93
Not assigned
Internal digital output 43, 44, 45
Relay 5: "Motor temperature trip"
Internal digital output 46, 47
Relay 6: "Automatic mode
(normal)"
Internal digital output 48, 49
Relay 7: "Speed 0"
Internal analog output 64, 65
Torque
Internal analog output 66, 67
Power
Signal designation
Function
Internal digital input 19, 20
+24 V DC; forced inverter inhibit
Internal digital input 6
Rapid stop global 1
Internal digital input 7
Separately driven fan of motor
activated
Internal digital input 17, 18
Forced power supply
disconnection
Internal digital input 21
External fault
Internal digital input 22
External warning
Internal digital input 23
Operation, bus
Internal digital input 24
Controller ON
Internal digital input 25
Fixed setpoint 1
Internal digital input 26
Fixed setpoint 2
Internal PTC thermistor
input 90, 91, 92, 93
Not assigned
Internal digital output 43, 44, 45
Relay 5: "Motor temperature trip"
Internal digital output 46, 47
Relay 6: "Automatic mode
(normal)"
Internal digital output 48, 49
Relay 7: "Speed 0"
Internal analog output 64, 65
Torque
Internal analog output 66, 67
Power
© Siemens AG 2014