SIEMENS
SINAMICS G180
Option descriptions
Standard options
4/3
Siemens D 18.1 · 2014
4
■
Options
(continued)
Advantage:
When the converter control voltage is supplied from the DC link,
this provides a backup function for drives with a coupled rotating
mass (e.g. fan drive). This means that the DC link of the converter
is maintained for a short time in the case of a temporary voltage
drop or power failure due to continued rotation of the rotating
mass on the motor. The control voltage for the converter is
backed-up until the DC link voltage fails due to standstill of the
rotating mass, or until the parameter "t-restart" causes switch-off.
D01, D02, D04, D05 and D06
Converter documentation
For the scope of the converter documentation, see the "Documen-
tation" section under "Services and documentation". A CD com-
prising a manual and IMS is supplied with every converter.
Note:
Please ask your Siemens sales partner if the documentation or
set of diagrams are required in a different language.
G13, G14, G15, G16 and G18
Accessories for IMS (Inverter Management Software)
G13
USB PROFIBUS interface (supplied separately packed)
G13
Softing PROFIBUS (PROFIBUS interface)
Active single-channel USB high-speed interface for connecting
a PC with IMS to a PROFIBUS network. The interface is suitable
for control and visualization tasks as well as for parameterization
and analysis applications via the IMS. All SINAMICS G180
converters in the PROFIBUS network can be addressed.
No additional power connection is required for this converter.
The cable on the converter has a double PROFIBUS SUB-D 9-pin
connection (socket/plug with end wiring) for connecting to
PROFIBUS. As a result, a simple connection is possible directly
on the SINAMICS G180 with PROFIBUS board (
G01
).
Note:
The installation notes in the help function of IMS must be ob-
served.
G14
Ethernet-PROFIBUS gateway
G14
Softing FG-100PB
Gateway between host systems on Ethernet and the PROFIBUS
bus system. Suitable for network configuration, device parame-
terization or acquisition of operating data. All SINAMICS G180
converters in the PROFIBUS system can be monitored and
parameterized.
The Ethernet-PROFIBUS gateway can be installed in the con-
verter cabinet or supplied separately packed. Please specify
your requirements in the order. The gateway is normally installed
at the most favorable transition point between Ethernet and
PROFIBUS.
Technical data:
•
Dimensions (W × H × D) 47 × 131 × 11 mm
•
Mounting on 35 mm DIN rail
•
Power supply 24 V DC (±20 %); 0.3 A
•
Operating temperature 0 °C to 55 °C
Scope of supply:
•
Ethernet interface on PROFIBUS
•
Installation manual
•
CD with Windows drivers
Note:
The installation notes in the help function of IMS must be
observed.
If the Ethernet-PROFIBUS gateway is supplied separately
with the converter, a separately power supply unit is required.
This is not part of the scope of supply.
Option
Description
C56
Connection for 230 V 1 AC 50 Hz external control voltage
provided by the customer,
no
UPS backup
With option
C56
the customer provides the control voltage
(230 V 1 AC +15 % -20 %; 47 to 63 Hz) for the converter.
The control voltage has no
UPS backup. The maximum current
consumption is 4 A.
C57
Connection for 230 V 1 AC 50 Hz external control voltage
provided by the customer, with UPS backup
With option
C57
the customer provides the control voltage
(230 V 1 AC +15 % -20 %; 47 to 63 Hz) for the converter.
The control voltage has
UPS backup. The maximum current
consumption is 4 A.
Y55
Connection for different level of single-phase AC control
voltage with 47 to 63 Hz provided by the customer, please
specify voltage
With option
Y55
the customer provides the control voltage for
the converter. The maximum current consumption is 4 A.
Option
Description
D01
Manual and set of diagrams in PDF format per e-mail
,
German/English
D02
Manual in PDF format, set of diagrams in DXF format per
e-mail
, German/English
D04
Manual and set of diagrams, single hardcopy
,
German/English
D05
Manual and set of diagrams in PDF format on CD
,
German/English
D06
Manual in PDF format, set of diagrams in DWG format on
CD
, German/English
© Siemens AG 2014