SIEMENS
SINAMICS G180
SINAMICS G180 cabinet units
SINAMICS G180 cabinet units
air-cooled and liquid-cooled
3/40
Siemens D 18.1 · 2014
3
■
Technical data
(continued)
690 V, 18-pulse
(continued)
Line voltage, supply system type
3 × 400, 415, 460, 500, 575,
690
V 3 AC IT
SINAMICS G180
cabinet units – air-cooled
6SE0180-
3HH44-8
■
A7
6SE0180-
3HH45-4
■
A7
6SE0180-
3HH46-0
■
A7
Converter type
(air-cooled)
2T3K-87606-947
2T3K-87606-953
2T3K-87606-958
SINAMICS G180
cabinet units – liquid-cooled
6SE0170-
3HH44-8
■
A7
6SE0170-
3HH45-4
■
A7
6SE0170-
3HH46-0
■
A7
Converter type
(liquid-cooled)
2T6K-77606-947
2T6K-77606-953
2T6K-77606-958
Electrical data at motor end
Type rating
1)
• at 50 Hz 690 V
kW
4700
5300
5800
• at 60 Hz 575 V
hp
5253
5923
6482
Output voltage
2)
V
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
0 ... 0.98 ×
V
line
Output current
• Continuous current
A
4800
5420
5940
• Short-time current
(60 s every 10 minutes) max.
A
5610
6040
6450
Overload capability
(60 s every 10 minutes) max.
%
17
11
9
Output power
kVA
5736
6477
7099
Output frequency, max.
Hz
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss
3)
kW
110
118
129
Rated efficiency
%
97.8
97.9
97.9
Electrical data at line end
Connected load
kVA
5244
5916
6482
Rated input voltage
V
3 × 690
3 × 690
3 × 690
Input current
• Continuous line current
A
3 × 1462
3 × 1651
3 × 1809
• Short-time line current (60 s) max.
A
3 × 1709
3 × 1840
3 × 1964
Line fuse (provided by customer)
gL (A)
1800
2000
2000 ... 2500
λ
line
1
1
1
Cos
ϕ
line
1
1
1
Radio interference suppression
acc. to EN 61800-3
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size
(dimensional drawing classification)
SL11
SL11
SL11
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
79
79
79
Standard converter dimensions
• Width
mm
10206
10206
10206
• Height
4)
mm
2112
2112
2112
• Depth
mm
605
605
605
Coolant requirements
m
3
/h
19550
23150
23150
Weight, approx.
kg
5930
6230
6530
Mechanical data for liquid-cooled cabinet units
Frame size
(dimensional drawing classification)
–
5)
–
5)
–
5)
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
77
77
77
Standard converter dimensions
• Width
mm
–
5)
–
5)
–
5)
• Height
mm
–
5)
–
5)
–
5)
• Depth
mm
–
5)
–
5)
–
5)
Coolant requirements
l/h
12000
12000
12000
Min. coolant pressure
bar
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
Coolant test pressure
bar
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
Max. coolant temperature
°C
38
30
28
Weight, approx.
kg
6090
6390
6690
For footnotes, see next page.
© Siemens AG 2014