Line side components for SINAMICS G150 NEMA type C enclosed chassis
Input line reactor
A minimum 2% input line reactor is recommended for most
installations. It can be included in the enclosure of the
enclosed chassis (option L23) or alternatively be mounted
externally, for example in an MCC with the other line side
components. The recommended type of input line reactor
is listed below.
A 2% to 3% inductor primarily assures the minimum current
form factor, protects the drive against excessive harmonic
currents and thus overloads, and improves the sensitivity
of the VFD to voltage spikes. If the drive is powered via a
separate transformer, or if the ratio between the line short
circuit capacity at the point of connection and the rated
drive output is low, the input line reactor may be omitted.
SINAMICS G150
NEMA Type C
Enclosed chassis
Output
(light overload)
at 460V or
575V, 60 Hz
Input line reactor
Motor (output) reactor
dV/dt filter plus VPL
Recommended
part #
Recommended
part #
Recommended
part #
Model No.
HP
Supply voltage 380 V to 480 V 3 ph. AC
6SL3710-1GE32-1CU3
150
6SL30000CE323AA0
6SL30002BE321AA0
6SL30002DE326AA0
6SL3710-1GE32-6CU3
200
6SL30000CE328AA0
6SL30002BE326AA0
6SL30002DE326AA0
6SL3710-1GE33-1CU3
250
6SL30000CE333AA0
6SL30002BE332AA0
6SL30002DE350AA0
6SL3710-1GE33-8CU3
300
6SL30000CE351AA0
6SL30002BE338AA0
6SL30002DE350AA0
6SL3710-1GE35-0CU3
400
6SL30000CE351AA0
6SL30002BE350AA0
6SL30002DE350AA0
6SL3710-1GE36-1CU3
500
6SL30000CE363AA0
6SL30002AE361AA0
6SL30002DE384AA0
6SL3710-1GE37-5CU3
600
6SL30000CE377AA0
6SL30002AE384AA0
6SL30002DE384AA0
6SL3710-1GE38-4CU3
700
6SL30000CE387AA0
6SL30002AE384AA0
6SL30002DE384AA0
6SL3710-1GE41-0CU3
800
6SL30000CE410AA0
6SL30002AE410AA0
6SL30002DE414AA0
Supply voltage 500 V to 600 V 3 ph. AC
6SL3710-1GF31-8CU3
150
6SL30000CH322AA0
6SL30002AH318AA0
6SL30002DH322AA0
6SL3710-1GF32-2CU3
200
6SL30000CH322AA0
6SL30002AH324AA0
6SL30002DH322AA0
6SL3710-1GF32-6CU3
250
6SL30000CH327AA0
6SL30002AH326AA0
6SL30002DH333AA0
6SL3710-1GF33-3CU3
300
6SL30000CH334AA0
6SL30002AH336AA0
6SL30002DH333AA0
6SL3710-1GF34-1CU3
400
6SL30000CH348AA0
6SL30002AH345AA0
6SL30002DH341AA0
6SL3710-1GF34-7CU3
450
6SL30000CH348AA0
6SL30002AH347AA0
6SL30002DH358AA0
6SL3710-1GF35-8CU3
600
6SL30000CH360AA0
6SL30002AH358AA0
6SL30002DH358AA0
6SL3710-1GF37-4CU3
700
6SL30000CH384AA0
6SL30002AH381AA0
6SL30002DH381AA0
6SL3710-1GF38-1CU3
800
6SL30000CH384AA0
6SL30002AH381AA0
6SL30002DH381AA0
Motor reactor (output reactor)
Motor reactors reduce the voltage load on the motor
windings by reducing the voltage gradients (dV/dt)
generated by the drive at the motor terminals. (Note that
a motor reactor does not increase the maximum motor
cable length for SINAMICS G150).
Output dV/dt-Filter plus VPL (Voltage Peak Limiter)
The dV/dt filter plus VPL allows the connection of non-
inverter duty motors to the SINAMICS G150 drive. For
motors insulated per NEMA MG1, part 30 (voltage peaks
<1,000 V and dV/dt <500 V/µs) the maximum allowable
motor cable length is up to 980’ (300 m) for a supply
voltage of 380-480 V, and 490’ (150 m) for 500-600 V.
Note that longer cable lengths of up to 450 m are possible,
but voltage peaks may exceed 1,000 V. Please refer to
engineering information for additional details.
The dv/dt filter plus VPL consists of two components: the
dv/dt reactor and the VPL (Voltage Peak Limiter), which
limits voltage peaks and returns the energy to the DC link.