SIEMENS
SINAMICS G150 NEMA
Type C enclosed chassis
3
Siemens D11.7
(Part 1) – 2013
3/11
Line side components for SINAMICS G150 NEMA type C enclosed chassis
SINAMICS G10 NEMA type C enclosed chassis do not include
any line side components (except for the optional line
reactor) – these components need to be added externally,
for example in an MCC.
To obtain the drive SCCR (short circuit current ratings) shown
in the technical data, it is necessary to combine it with the
fuses and fuse bases listed in the manual, and shown in the
table below (substitutes are not permitted). Also, a UL-listed
circuit breaker for motor branch circuit protection (with
minimum SCCR as required for the drive) is required, which
may not exceed the maximum current rating shown.
The SCCR shown below is the value applicable to the
drive when combined with the specified fuses, and the
recommended circuit breaker and, if applicable,
recommended contactor (used as input, output and/or
bypass contactor).
SINAMICS G150
NEMA Type C
Enclosed chassis
Output
(light overload)
at 460 V or
575 V, 60 Hz
Circuit breaker
Semiconductor fuses
Contactor
max.
rating
Recommended
part #
SCCR
max.
1)
Fuse
required
part #
Fuse base
required
part #
Recommended
part #
SCCR
max
1) 2)
Model No.
HP
A
kA
per phase
per phase
Siemens
kA
Supply voltage 380 V to 480 V 3 ph. AC
6SL3710-1GE32-1CU3
150
500
HJX3B300
65
3NE12302
3NH3320
3RT10666AF36
65
6SL3710-1GE32-6CU3
200
600
HJX3B400
65
3NE13312
3NH3320
3RT10766AF36
65
6SL3710-1GE33-1CU3
250
700
HLX3B500
65
3NE13342
3NH3420
3RT10766AF36
65
6SL3710-1GE33-8CU3
300
800
HLX3B600
65
3NE13342
3NH3420
3RT10766AF36
65
6SL3710-1GE35-0CU3
400
1200
HMX3B800
65
3NE14362
3NH3420
3RT10766AF36
65
6SL3710-1GE36-1CU3
500
1200
HMX3B800
65
3NE14382
3NH3420
40NH32AF
65
6SL3710-1GE37-5CU3
600
1600
HNX3X100
65
3NE14482
3NH3420
40NH32AF
65
6SL3710-1GE38-4CU3
700
2000
HNX3X120
65
2x 3NE14362
2x 3NH3420
40PH32AF
65
6SL3710-1GE41-0CU3
800
2000
HPX3X160
65
2x 3NE14372
2x 3NH3420
40PH32AF
65
Supply voltage 500 V to 600 V 3 ph. AC
6SL3710-1GF31-8CU3
150
400
HJX3B300
25
3NE12272
3NH3320
3RT10666AF36
25
6SL3710-1GF32-2CU3
200
500
HJX3B350
25
3NE12302
3NH3320
3RT10666AF36
25
6SL3710-1GF32-6CU3
250
600
HJX3B350
25
3NE13312
3NH3320
3RT10666AF36
25
6SL3710-1GF33-3CU3
300
800
HLX3B500
25
3NE13342
3NH3420
3RT10766AF36
25
6SL3710-1GF34-1CU3
400
1000
HLX3B600
25
3NE13342
3NH3420
3RT10766AF36
25
6SL3710-1GF34-7CU3
450
1000
HMX3B800
35
3NE14352
3NH3420
3RT10766AF36
30
6SL3710-1GF35-8CU3
600
1200
HMX3B800
35
3NE14472
3NH3420
40NH32AF
35
6SL3710-1GF37-4CU3
700
1600
HNX3X100
35
3NE14482
3NH3420
40PH32AF
35
6SL3710-1GF38-1CU3
800
2000
HNX3X120
35
2x 3NE13342
2x 3NH3420
40PH32AF
35
1
) The short circuit current ratings (SCCR) listed above are the SCCR for the enclosed drive unit when used with the recommended components.
2
) The SCCR listed for the contactor is the combination SCCR when the contactor is used in combination with the recommended circuit breaker.
3
) The circuit breaker part # is for the circuit breaker frame only, and does not include any accessories required for connection (for example lugs).
NOTE:
SCCR ratings are provided for information only, and are based on published catalog data at the time this catalog was written. Since the data may be
revised, please check for accuracy against the most current catalogs and/or manuals, and/or the device nameplates.