Description of options
G20
CBC10 communication board CANopen
The CBC10 Communication Board is used to interface the
CU320-2 Control Unit of the SINAMICS G150 to the CAN
(Controller Area Network) protocol. The board’s driver
software fulfills the standards of the following CANopen
specification of the CiA organization (CAN in Automation):
• Communication profiles in accordance with DS 301
• Drive profile in accordance with DSP 402 (in this case Pro
file Velocity Mode)
• EDS (Electronic Data Sheet) in accordance with DSP 306
• Operating status signaling in accordance with DSP 305
The CBC10 Communication Board plugs into the option
slot on the CU320-2 Control Unit. The CAN interface on the
CBC10 has 2 SUB-D connections for input and output.
G33
CBE20 communication board Ethernet
The CBE20 communication board connects the CU320-2 DP
or CU320-2 PN Control Unit to an additional communications
bus. The CBE20 can be parameterized to connect to either:
• SINAMICS Link high speed peer-to-peer communications
with other CBE20 modules plugged into the CU320-2
control units of other SINAMICS drives, up to 64 nodes.
• PROFINET I/O network, 100 Mbit/s full-duplex, supports
real-time classes RT (Real-Time) and IRT (Isochronous
Real-Time). (Only one communication interface can be
used in isochronous operation when operating the CBE20
in a CU320-2 DP or PN Control Unit).
• EtherNet/IP (EtherNet Industrial Protocol) is an open
standard predominantly used in the automation industry.
EtherNet/IP is supported by the Open DeviceNet Vendor
Association (ODVA).
In addition, the CBE20 allows on a PROFINET or EtherNet/IP
network:
• Standard Ethernet TCP/IP communication for engineering
processes using the STARTER commissioning tool
The CBE20 Communication Board plugs into the option slot
on the CU320-2 Control Unit. It has 4x RJ45 Ethernet ports.
Description of the CBE20 Communication Board Ethernet
Chapter 4.
G51
TM150 Terminal Module (RTD Monitoring)
The TM150 RTD module is suitable for monitoring temperature
sensors type Pt100 or Pt1000 (Platinum RTD 100 ohm or
1,000 ohm), KTY84, PTC thermistor or a temperature switch
contact (NC). Up to 12 sensors in 2-wire connection or up to
6 sensors in 3- or 4-wire connection can be connected to one
TM150.
Temperature values from the TM150 are available for further
processing, for transmission to the process control system
via bus communications and can be displayed on the AOP30.
Note: TM150 inputs are not electrically isolated. Only
temperature sensors isolated per IEC 61800-5-1 may be
connected to terminals “+Temp” and “-Temp”. Failure to
observe these instructions can result in electric shock!
K50
SMC30 sensor module for speed feedback
The SMC30 encoder module is required to connect a speed
feedback encoder to the drive. Rotary pulse encoder signals
are converted here and made available for evaluation via the
DRIVE-CLiQ interface of the controller.
The following encoders are supported by the SMC30:
• TTL encoders
• HTL encoders
The motor temperature can also be detected using a
KTY84-130 sensor or PTC thermistors.
Refer to engineering information for details.
K95
CU320-2 PN Control Unit
Replace the standard CU320-2 DP with PROFIBUS port by the
CU320-2 PN with PROFINET port.
L23
Input line reactor
This option is to include an input line reactor inside the
enclosure. Alternatively the line reactor can be mounted
externally. A minimum 2% input line reactor is
recommended for most installations.
If the drive is powered via a separate transformer, or if the
ratio between the line short circuit capacity at the point of
connection and the rated drive output is low, the input line
reactor may be omitted.
A 2% to 3% inductor primarily assures the minimum current
form factor, protects the drive against excessive harmonic
currents and thus overloads, and improves the sensitivity of
the VFD to voltage spikes.
L55
Enclosure space heater
Space heaters are recommended at low ambient
temperatures and high levels of humidity to prevent
condensation. One 90 W heater is provided for each cabinet
<32” (800 mm) width. For cabinets exceeding this width,
two heaters will be installed.
M06
Base (plinth) 4” (100 mm) high
The 4” enclosure base allows larger
bending radii for cables (cable
entry from below) and routing them
within the base. It is delivered already
mounted to the enclosure. The height
of the operator panel changes
accordingly. The base is always
colored RAL 7022 (umbra grey).
A special color is not possible.
Enclosure with option M06