SIEMENS
3/50
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Load-side power components > Sine-wave filters
■
Overview
Sine-wave filters are available in the voltage range 380 V to
480 V up to a type rating of 250 kW, and in the voltage range
500 V to 600 V up to a type rating of 132 kW.
The sine-wave filter at the converter output supplies almost per-
fect sinusoidal voltages on the motor so that standard motors
can be used without special cables or power derating. Standard
cables can be used.
Note the following when a sine-wave filter is used:
•
The output frequency is limited to max. 150 Hz
(at 380 to 480 V) and 115 Hz (at 500 to 600 V).
•
The maximum output voltage is limited to approx. 85% of the
input voltage.
•
Maximum permissible motor cable lengths:
- Unshielded cable: 450 m
- Shielded cable: 300 m
•
During commissioning, the pulse frequency is increased to
double the factory setting. This induces current derating,
which must be applied to the built-in units' rated currents
listed in the technical specifications.
Note:
The reduced voltage at the motor terminals compared to the
rated motor voltage means that the motor reaches the field
weakening range earlier.
The sine-wave filter may be operated only when the motor is
connected; sine-wave filters are not no-load-proof!
For further information on sine-wave filters, please refer to the
SINAMICS Low Voltage Engineering Manual.
■
Selection and ordering data
Suitable for
Power Module
Type rating of
the Power
Module at 400 V
or 500 V
Sine-wave filter
kW
Article No.
380 ... 480 V 3 AC
6SL3310-1GE32-1AA3
6SL3310-1GE32-6AA3
110
132
6SL3000-2CE32-3AA0
6SL3310-1GE33-1AA3
160
6SL3000-2CE32-8AA0
6SL3310-1GE33-8AA3
200
6SL3000-2CE33-3AA0
6SL3310-1GE35-0AA3
250
6SL3000-2CE34-1AA0
500 ... 600 V 3 AC
6SL3310-1GF31-8AA3
6SL3310-1GF32-2AA3
110
132
6SL3000-2CF31-7AA0
© Siemens AG 2015