SIEMENS
3/47
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Load-side power components > dv/dt filters compact plus VPL
■
Technical specifications
Line voltage
380 ... 480 V 3 AC
dv/dt filter compact plus VPL
6SL3000-2DE32-6EA0
6SL3000-2DE35-0EA0
6SL3000-2DE38-4EA0
6SL3000-2DE41-1EA0
Rated current
A
260
490
840
1405
I
th max
A
260
490
840
1405
Power loss, max.
• At 50 Hz 400 V
kW
0.21
0.29
0.518
Reactor: 1.027
VPL: 0.127
Total: 1.154
• At 60 Hz 460 V
kW
0.215
0.296
0.529
Reactor: 1.077
VPL: 0.12
Total: 1.197
• At 150 Hz 400 V
kW
0.255
0.344
0.609
Reactor: 1.354
VPL: 0.09
Total: 1.444
Power connection,
input and output side
Hole for M10
Hole for M10
Hole for M12
2 x elongated holes,
14 x 18 mm
• Conductor cross section, max. (IEC)
Provided for busbar con-
nection
Provided for busbar con-
nection
Provided for busbar con-
nection
Provided for busbar con-
nection
DC-link connection,
DCPS, DCNS
Threaded socket M8
Threaded socket M8
Hole for M8
Hole for M8
• Conductor cross section, max. (IEC)
mm
2
16
25
50
95
PE/GND connection
Threaded socket M6
Threaded socket M6
Threaded socket M6
Threaded socket M6
(reactor and VPL)
Cable length, max.
between dv/dt filter and motor
• Shielded
m
100
100
100
100
• Unshielded
m
150
150
150
150
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
• Width
mm
310
350
440
Reactor: 430
VPL: 277
• Height
mm
283
317
369
Reactor: 385
VPL: 360
• Depth
mm
238
260
311
Reactor: 323
VPL: 291
Weight, approx.
kg
41
61
103
Reactor: 168.8
VPL: 19.2
Total: 188
Approvals, according to
cURus
cURus
cURus
cURus
Suitable for
Power Module
6SL3310-1GE32-1AA3
(110 kW)
6SL3310-1GE32-6AA3
(132 kW)
6SL3310-1GE33-1AA3
(160 kW)
6SL3310-1GE33-8AA3
(200 kW)
6SL3310-1GE35-0AA3
(250 kW)
6SL3310-1GE36-1AA3
(315 kW)
6SL3310-1GE37-5AA3
(400 kW)
6SL3310-1GE38-4AA3
(450 kW)
6SL3310-1GE41-0AA3
(560 kW)
© Siemens AG 2015