SIEMENS
3/45
Siemens D 11 · 2015
■
Technical specifications
(continued)
3
SINAMICS G130
Drive converter chassis units
Load-side power components > dv/dt filters plus VPL
Note:
Two dv/dt reactors are required for Power Modules with a
type rating of 710 kW and 800 kW.
The listed technical specifications refer to one
dv/dt reactor.
1)
Longer cable lengths for specific configurations are available on request.
Line voltage
660 ... 690 V 3 AC
dv/dt filter plus VPL
6SL3000-2DH34-1AA0
6SL3000-2DH35-8AA0
6SL3000-2DH38-1AA0
I
th max
A
410
575
810
Degree of protection
IP00
IP00
IP00
Cable length, max.
between dv/dt filter and motor
1)
• Shielded
m
300
300
300
• Unshielded
m
450
450
450
Approvals, according to
cURus
cURus
cURus
dv/dt reactor
Power loss
• At 50 Hz
kW
0.786
0.862
0.828
• At 60 Hz
kW
0.826
0.902
0.867
• At 150 Hz
kW
0.884
0.964
0.927
Connections
• To Power Module
1 × hole for M12
1 × hole for M12
2 × holes for M12
• To load
1 × hole for M12
1 × hole for M12
2 × holes for M12
• PE
M6 screw
M6 screw
M6 screw
Dimensions
• Width
mm
460
460
445
• Height
mm
385
385
385
• Depth
mm
312
312
312
Weight, approx.
kg
147
172
160
Voltage Peak Limiter (VPL)
Power loss
• At 50 Hz
kW
0.051
0.063
0.106
• At 60 Hz
kW
0.048
0.059
0.1
• At 150 Hz
kW
0.043
0.054
0.091
Connections
• To dv/dt reactor
1 × hole for M8
1 × hole for M8
1 × hole for M10
• To DC link
1 × hole for M8
1 × hole for M8
1 × hole for M10
• PE
M8 stud
M8 stud
M8 stud
Dimensions
• Width
mm
309
309
309
• Height
mm
1312.5
1312.5
1312.5
• Depth
mm
400
400
400
Weight, approx.
kg
48
48
72
Suitable for
Power Module
6SL3310-1GH34-1AA3 (400 kW)
6SL3310-1GH34-7AA3 (450 kW)
6SL3310-1GH35-8AA3 (560 kW)
6SL3310-1GH37-4AA3 (710 kW)
6SL3310-1GH38-1AA3 (800 kW)
© Siemens AG 2015