SIEMENS
3/30
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Line-side power components > Recommended line-side system components
■
Selection and ordering data
The table below lists recommended ratings for input-side switch-
ing and fuse protection elements according to IEC standards.
Further information about the main contactors, switch discon-
nectors, fuses and circuit breakers specified in the table can be
found in Catalog LV 10.
*)
The circuit breakers must always be switched ON and OFF by the
sequence control. An interlocking set 3WL9111-0BA21-0AA0 as described
in Catalog LV 10 should be provided for the circuit breakers in order to
exclude the risk of unintentional manual operation. Manual operation
bypasses the pre-charging circuit and can therefore destroy the Power
Module.
Type rating
(for 400V, 500V or
690V)
Rated input current
Assignment to
Power Module
Line contactor
Fixed-mounted
circuit breaker
Switch disconnector
for cable protection fuses
incl. semiconductor pro-
tection of type 3NE1
kW
A
Typ 6SL3310-...
Type
Type
Type
380 ... 480 V 3 AC
110
229
1GE32-1AA3
3RT1456-…..
–
3KL5530-…..
132
284
1GE32-6AA3
3RT1466-…..
–
3KL5730-…..
160
338
1GE33-1AA3
3RT1466-…..
–
3KL5730-…..
200
395
1GE33-8AA3
3RT1476-…..
–
3KL6130-…..
250
509
1GE35-0AA3
3RT1476-…..
–
3KL6130-…..
315
629
1GE36-1AA3
3RT1476-…..
–
3KL6230-…..
400
775
1GE37-5AA3
3RT1466-…..
(3 units)
–
3KL6230-…..
450
873
1GE38-4AA3
–
3WL1110-…
*)
–
560
1024
1GE41-0AA3
–
3WL1112-…
*)
–
500 ... 600 V 3 AC
110
191
1GF31-8AA3
3RT1456-…..
–
3KL5530-…..
132
242
1GF32-2AA3
3RT1456-…..
–
3KL5530-…..
160
270
1GF32-6AA3
3RT1466-…..
–
3KL5730-…..
200
343
1GF33-3AA3
3RT1466-…..
–
3KL5730-…..
250
426
1GF34-1AA3
3RT1476-…..
–
3KL6130-…..
315
483
1GF34-7AA3
3RT1476-…..
–
3KL6130-…..
400
598
1GF35-8AA3
3RT1476-…..
–
3KL6230-…..
500
764
1GF37-4AA3
3RT1466-…..
(3 units)
–
3KL6230-…..
560
842
1GF38-1AA3
–
3WL1210-…
*)
–
660 ... 690 V 3 AC
75
93
1GH28-5AA3
3RT1446-…..
–
3KL5230-…..
90
109
1GH31-0AA3
3RT1446-…..
–
3KL5230-…..
110
131
1GH31-2AA3
3RT1446-…..
–
3KL5530-…..
132
164
1GH31-5AA3
3RT1456-…..
–
3KL5530-…..
160
191
1GH31-8AA3
3RT1456-…..
–
3KL5530-…..
200
224
1GH32-2AA3
3RT1456-…..
–
3KL5530-…..
250
270
1GH32-6AA3
3RT1466-…..
–
3KL5730-…..
315
343
1GH33-3AA3
3RT1466-…..
–
3KL5730-…..
400
426
1GH34-1AA3
3RT1476-…..
–
3KL6130-…..
450
483
1GH34-7AA3
3RT1476-…..
–
3KL6130-…..
560
598
1GH35-8AA3
3RT1476-….
–
3KL6230-…..
710
764
1GH37-4AA3
3RT1466-…..
(3 units)
–
3KL6230-…..
800
842
1GH38-1AA3
–
3WL1210-…
*)
–
© Siemens AG 2015