SIEMENS
3/20
Siemens D 11 · 2015
■
Technical specifications
(continued)
3
SINAMICS G130
Drive converter chassis units
Power Modules
Note:
The power data in hp units is based on the NEC/CEC stan-
dards for the North American market.
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 640 V.
2)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or 150%
for 10 s with a load cycle duration of 300 s
3)
The base-load current
I
L
is based on a load cycle of 150% for 60 s or 160%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
).
4)
If the auxiliary supply is to be fed in separately from the load supply, e.g. if
the control should be able to continue communication when the line
voltage fails.
5)
The minimum current required to reliably trigger 3NE1 protective devices.
6)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating conditions.
7)
Longer cable lengths for specific configurations are available on request.
Line voltage
660 ... 690 V 3 AC
Power Modules
6SL3310-
1GH32-6AA3
6SL3310-
1GH33-3AA3
6SL3310-
1GH34-1AA3
6SL3310-
1GH34-7AA3
6SL3310-
1GH35-8AA3
6SL3310-
1GH37-4AA3
6SL3310-
1GH38-1AA3
Type rating
• For
I
L
at 50 Hz 690 V
1)
kW
250
315
400
450
560
710
800
• For
I
H
at 50 Hz 690 V
1)
kW
200
250
315
400
500
560
710
Output current
• Rated current
I
n
A
260
330
410
465
575
735
810
• Base-load current
I
L
2)
A
250
320
400
452
560
710
790
• Base-load current
I
H
3)
A
233
280
367
416
514
657
724
Input current
• Rated input current
A
270
343
426
483
598
764
842
• Input current, max.
A
410
525
655
740
918
1164
1295
•
Current requirement, 24 V DC auxiliary
power supply
4)
A
0.9
0.9
1
1
1
1.25
1.25
Minimum short-circuit current
5)
A
3600
5200
5200
6200
8400
10500
10400
Heat loss, max.
6)
at 50 Hz 690 V
kW
4
5
6.7
7.3
8.6
12.1
13.4
Cooling air requirement
m
3
/s
0.36
0.36
0.78
0.78
0.78
1.48
1.48
Cable length, max.
between Power Module and motor
7)
• Shielded
m
300
300
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
450
450
Degree of protection
IP20
IP20
IP00
IP00
IP00
IP00
IP00
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
69/73
69/73
70/73
70/73
70/73
73/75
73/75
Line connection
U1, V1, W1
M10 screw
M10 screw
2 × M12
screws
2 × M12
screws
2 × M12
screws
3 × M12
screws
3 × M12
screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
4 × 240
4 × 240
4 × 240
6 × 240
6 × 240
Motor connection
U2/T1, V2/T2, W2/T3
M10 screw
M10 screw
2 × M12
screws
2 × M12
screws
2 × M12
screws
3 × M12
screws
3 × M12
screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
4 × 240
4 × 240
4 × 240
6 × 240
6 × 240
PE1/GND connection
M10 screw
M10 screw
M12 screw
M12 screw
M12 screw
2 × M12
screws
2 × M12
screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
2 × 240
2 × 240
4 × 240
4 × 240
PE2/GND connection
M10 screw
M10 screw
2 × M12
screws
2 × M12
screws
2 × M12
screws
3 × M12
screws
3 × M12
screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
4 × 240
4 × 240
4 × 240
6 × 240
6 × 240
Dimensions
• Width
mm
326
326
503
503
503
909
909
• Height
mm
1533
1533
1506
1506
1506
1510
1510
• Depth
mm
545
545
540
540
540
540
540
Weight, approx.
kg
176
176
294
294
294
530
530
Frame size
GX
GX
HX
HX
HX
JX
JX
© Siemens AG 2015