SIEMENS
3/17
Siemens D 11 · 2015
■
Technical specifications
(continued)
3
SINAMICS G130
Drive converter chassis units
Power Modules
Note:
The power data in hp units is based on the NEC/CEC stan-
dards for the North American market.
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 500 V.
2)
Rated output of a typical 6-pole standard induction motor based
on
I
L
or
I
H
for 3 AC 60 Hz 575 V.
3)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or 150%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
).
4)
The base-load current
I
L
is based on a load cycle of 150% for 60 s or 160%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
).
5)
If the auxiliary supply is to be fed in separately from the load supply, e.g. if
the control should be able to continue communication when the line
voltage fails.
6)
The minimum current required to reliably trigger 3NE1 protective devices.
7)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating conditions.
8)
Longer cable lengths for specific configurations are available on request.
Line voltage
500 ... 600 V 3 AC
Power Modules
6SL3310-
1GF31-8AA3
6SL3310-
1GF32-2AA3
6SL3310-
1GF32-6AA3
6SL3310-
1GF33-3AA3
6SL3310-
1GF34-1AA3
Type rating
• For
I
L
at 50 Hz 500 V
1)
kW
110
132
160
200
250
• For
I
H
at 50 Hz 500 V
1)
kW
90
110
132
160
200
• For
I
L
at 60 Hz 575 V
2)
hp
150
200
250
300
400
• For
I
H
at 60 Hz 575 V
2)
hp
150
200
200
250
350
Output current
• Rated current
I
n
A
175
215
260
330
410
• Base-load current
I
L
3)
A
171
208
250
320
400
• Base-load current
I
H
4)
A
157
192
233
280
367
Input current
• Rated input current
A
191
224
270
343
426
• Input current, max.
A
279
341
410
525
655
•
Current requirement, 24 V DC auxiliary
power supply
5)
A
0.9
0.9
0.9
0.9
1
Minimum short-circuit current
6)
A
2400
3000
3600
5200
5200
Power loss, max.
7)
• At 50 Hz 500 V
kW
2.8
3.2
3.7
4.6
6.1
• At 60 Hz 575 V
kW
3.2
3.6
4.1
5.1
7.1
Cooling air requirement
m
3
/s
0.36
0.36
0.36
0.36
0.78
Cable length, max.
between Power Module and motor
8)
• Shielded
m
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
IP00
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
69/73
69/73
69/73
69/73
70/73
Line connection
U1, V1, W1
M10 screw
M10 screw
M10 screw
M10 screw
2 × M12 screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
2 × 240
4 × 240
Motor connection
U2/T1, V2/T2, W2/T3
M10 screw
M10 screw
M10 screw
M10 screw
2 × M12 screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
2 × 240
4 × 240
PE1/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
2 × 240
2 × 240
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
2 x M12 screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
2 × 240
4 × 240
Dimensions
• Width
mm
326
326
326
326
503
• Height
mm
1533
1533
1533
1533
1506
• Depth
mm
545
545
545
545
540
Weight, approx.
kg
176
176
176
176
294
Frame size
GX
GX
GX
GX
HX
© Siemens AG 2015