SIEMENS
3/16
Siemens D 11 · 2015
■
Technical specifications
(continued)
3
SINAMICS G130
Drive converter chassis units
Power Modules
Note:
The power data in hp units is based on the NEC/CEC stan-
dards for the North American market.
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 400 V.
2)
Rated output of a typical 6-pole standard induction motor based
on
I
L
or
I
H
for 3 AC 60 Hz 460 V.
3)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or 150%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
).
4)
The base-load current
I
L
is based on a load cycle of 150% for 60 s or 160%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
).
5)
If the auxiliary supply is to be fed in separately from the load supply, e.g. if
the control should be able to continue communication when the line
voltage fails.
6)
The minimum current required to reliably trigger 3NE1 protective devices.
7)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating conditions.
8)
Longer cable lengths for specific configurations are available on request.
Line voltage
380 ... 480 V 3 AC
Power Modules
6SL3310-1GE36-1AA3
6SL3310-1GE37-5AA3
6SL3310-1GE38-4AA3
6SL3310-1GE41-0AA3
Type rating
• For
I
L
at 50 Hz 400 V
1)
kW
315
400
450
560
• For
I
H
at 50 Hz 400 V
1)
kW
250
315
400
450
• For
I
L
at 60 Hz 460 V
2)
hp
500
600
700
800
• For
I
H
at 60 Hz 460 V
2)
hp
350
450
600
700
Output current
• Rated current
I
n
A
605
745
840
985
• Base-load current
I
L
3)
A
590
725
820
960
• Base-load current
I
H
4)
A
460
570
700
860
Input current
• Rated input current
A
629
775
873
1024
• Input current, max.
A
967
1188
1344
1573
•
Current requirement, 24 V DC auxiliary
power supply
5)
A
1
1
1
1.25
Minimum short-circuit current
6)
A
10000
10500
16000
18400
Power loss, max.
7)
• At 50 Hz 400 V
kW
7.2
8.5
9.1
12.7
• At 60 Hz 460 V
kW
8.1
9.4
10.2
14.5
Cooling air requirement
m
3
/s
0.78
0.78
0.78
1.48
Cable length, max.
between Power Module and motor
8)
• Shielded
m
300
300
300
300
• Unshielded
m
450
450
450
450
Degree of protection
IP00
IP00
IP00
IP00
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
70/73
70/73
70/73
72/75
Line connection
U1, V1, W1
2 × M12 screws
2 × M12 screws
2 × M12 screws
3 × M12 screws
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
6 × 240
Motor connection
U2/T1, V2/T2, W2/T3
2 × M12 screws
2 × M12 screws
2 × M12 screws
3 × M12 screws
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
6 × 240
PE1/GND connection
M12 screw
M12 screw
M12 screw
2 × M12 screws
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
4 × 240
PE2/GND connection
2 × M12 screws
2 × M12 screws
2 × M12 screws
3 × M12 screws
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
6 × 240
Dimensions
• Width
mm
503
503
503
909
• Height
mm
1506
1506
1506
1510
• Depth
mm
540
540
540
540
Weight, approx.
kg
294
294
294
530
Frame size
HX
HX
HX
JX
© Siemens AG 2015