SIEMENS
3/15
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Power Modules
■
Technical specifications
Note:
The power data in hp units is based on the NEC/CEC stan-
dards for the North American market.
Line voltage
380 ... 480 V 3 AC
Power Modules
6SL3310-
1GE32-1AA3
6SL3310-
1GE32-6AA3
6SL3310-
1GE33-1AA3
6SL3310-
1GE33-8AA3
6SL3310-
1GE35-0AA3
Type rating
• For
I
L
at 50 Hz 400 V
1)
kW
110
132
160
200
250
• For
I
H
at 50 Hz 400 V
1)
kW
90
110
132
160
200
• For
I
L
at 60 Hz 460 V
2)
hp
150
200
250
300
400
• For
I
H
at 60 Hz 460 V
2)
hp
150
200
200
250
350
Output current
• Rated current
I
n
A
210
260
310
380
490
• Base-load current
I
L
3)
A
205
250
302
370
477
• Base-load current
I
H
4)
A
178
233
277
340
438
Input current
• Rated input current
A
229
284
338
395
509
• Input current, max.
A
335
410
495
606
781
• Current requirement, 24 V DC auxiliary
power supply
5)
A
0.8
0.8
0.9
0.9
0.9
Minimum short-circuit current
6)
A
3000
3600
4400
4400
8000
Power loss, max.
7)
• At 50 Hz 400 V
kW
2.4
3.2
3.9
4.3
5.6
• At 60 Hz 460 V
kW
2.6
3.3
4.4
4.9
6.1
Cooling air requirement
m
3
/s
0.17
0.23
0.36
0.36
0.36
Cable length, max.
between Power Module and motor
8)
• Shielded
m
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
IP20
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
64/67
64/67
69/73
69/73
69/73
Line connection
U1, V1, W1
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
2 × 240
Motor connection
U2/T1, V2/T2, W2/T3
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
2 × 240
PE1/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
2 × 240
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
2 × 240
Dimensions
• Width
mm
326
326
326
326
326
• Height
mm
1400
1400
1533
1533
1533
• Depth
mm
356
356
545
545
545
Weight, approx.
kg
104
104
176
176
176
Frame size
FX
FX
GX
GX
GX
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 400 V.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 60 Hz 460 V.
3)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or 150%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
)
4)
The base-load current
I
H
is based on a load cycle of 150% for 60 s or 160%
for 10 s with a load cycle duration of 300 s
(
see Technical specifications
→
Overload capability
).
5)
If the auxiliary supply is to be fed in separately from the load supply, e.g. if
the control should be able to continue communication when the line voltage
fails
6)
The minimum current required to reliably trigger 3NE1 protective devices.
7)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating condition.
8)
Longer cable lengths for specific configurations are available on request.
© Siemens AG 2015