Siemens D 11 · 2015
■
Function
(continued)
3
SINAMICS G130
Drive converter chassis units
75 kW to 800 kW
Software and protective functions
The software functions available as standard are described below:
Software and protective functions
Description
Setpoint specification
The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer
setpoint or jog setpoint, externally via the communications interface or an analog input on the customer terminal
block. The internal fixed setpoint and the motorized potentiometer setpoint can be switched or adjusted via control
commands from any interface.
Motor identification
The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control
of the drive.
Ramp-function generator
A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with
adjustable rounding times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and
braked. As a consequence, this avoids the drive train from being overloaded and reduces the stress on mechanical
components. The down ramps can be parameterized separately for quick stop.
V
dc max
controller
The V
dc max
controller automatically prevents overvoltages in the DC link, if the set down ramp is too short, for exam-
ple. This may also extend the set ramp-down time.
Vdc_min control
For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents
fault trips. The converter remains operational as long as the drive can provide regenerative energy as a result of its
motion and the DC-link voltage does not drop below the shutdown threshold. When the line supply recovers within this
time, the drive is again accelerated up to its speed setpoint.
Automatic restart
1)
The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to
the current speed setpoint.
Flying restart
1)
The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing
capability provided by the optional VSM10 Voltage Sensing Module, the flying restart time for large induction motors
can be significantly reduced because the motor does not need to be de-magnetized.
Technology controller
The technology controller function module allows simple control functions to be implemented, e.g. level control or
volumetric flow control. The technology controller is designed as a PID controller. The differentiator can be switched to
the control deviation channel or to the actual value channel (factory setting). The P, I, and D components can be set
separately.
Free function blocks
Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling
the SINAMICS G130. The blocks can be programmed by means of an operator panel or the STARTER commissioning
tool.
Drive Control Chart (DCC)
Drive Control Chart (DCC) is an additional tool for the easy configuration of technology functions for the SINAMICS
G130. The block library contains a large selection of control, arithmetic and logic blocks as well as extensive open-
loop and closed-loop control functions. The user-friendly DCC editor enables easy graphics-based configuration,
allows control loop structures to be clearly represented and provides a high degree of reusability of charts that have
already been created. DCC is an add-on to the STARTER commissioning tool.
I
²
t
detection for motor protection
A motor model stored in the converter software calculates the motor temperature based on the current speed and
load. More exact measurement of the temperature, which also takes into account the influence of the ambient temper-
ature, is possible by means of direct temperature measurement using KTY84 sensors in the motor winding.
Motor temperature evaluation
Motor protection by evaluating a KTY84, PTC or Pt100 temperature sensor. When a KTY84 sensor is connected, the
limit values can be set for alarm or trip. When a PTC thermistor is connected, the system reaction to triggering of the
thermistor (alarm or trip) can be defined.
Motor blocking protection
A blocked motor is detected and protected against thermal overloading by a fault trip.
Essential service mode
Special converter operating mode that increases the availability of the drive system, e.g. in the event of a fire.
Bypass
This circuit allows the motor to be operated via the converter or directly on the line supply.
Brake control
"Simple brake control" for control of holding brakes:
The holding brake is used to secure drives against unwanted motion when deactivated.
"Extended brake control" function module for complex brake control, e.g. for motor holding brakes and operational
brakes:
When braking with a feedback signal, the brake control reacts to the feedback signal contacts of the brake.
Write protection
Write protection to prevent unintentional changing of the setting parameters (without password function).
Know-how protection
Know-how protection for encrypting stored data, e.g. to protect configuration know-how, and to protect against
changes and duplication (with password function).
Web server
The integrated web server provides information about the drive unit via its web pages. The web server is accessed
using an Internet browser via unsecured (http) or secured transmission (https).
Power unit protection
Description
Ground fault monitoring at the output
A ground fault at the output is detected by a total current monitor and results in shutdown in grounded systems.
Electronic short-circuit protection
at the output
A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is
detected and the converter shuts down with a "fault".
Thermal overload protection
An alarm is issued first when the overtemperature threshold responds. If the temperature rises further, the device
either shuts down or independently adjusts the pulse frequency or output current so that a reduction in the thermal
load is achieved. Once the cause of the fault has been eliminated (e.g. cooling has been improved), the original oper-
ating values are automatically resumed.
1)
Factory setting: Not activated (can be parameterized).