SIEMENS
4/41
Siemens D 11 · 2015
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
■
Configuration
Cable cross-sections and connections
The following tables list the recommended and maximum possi-
ble cable connections at the line and motor ends for a single
connection (versions A and C) and a parallel connection
(version A).
The recommended cross-sections are based on the specified
fuses. They are valid for a three-conductor copper cable routed
horizontally in air with PVC insulation and a permissible conduc-
tor temperature of 70° C (e.g. Protodur NYY or NYCWY) at an
ambient temperature of 40° C and individual routing.
For deviating conditions (cable routing, cable accumulation, am-
bient temperature), the appropriate correction factors according
to IEC 60364-5-52 must be taken into account.
For further information, please refer to the SINAMICS Low
Voltage Engineering Manual.
Single connection
Type
rating
Converter cabinet unit
Line connection
Motor connection
Cabinet grounding
SINAMICS G150,
versions A and C
Recommen-
ded cross-
section
1)
Maximum
cable cross-
section
Fixing screws
Recommen-
ded cross-
section
1)
Maximum
cable cross-
section
Fixing screws
Fixing screws
Remark
IEC
IEC
IEC
IEC
kW
6SL3710-...
mm
2
mm
2
mm
2
mm
2
380 ... 480 V 3 AC
110
1GE32-1 . A3
2 × 70
4 × 240
M12
2 × 50
2 × 150
M12
M12
132
1GE32-6 . A3
2 × 95
4 × 240
M12
2 × 70
2 × 150
M12
M12
160
1GE33-1 . A3
2 × 120
4 × 240
M12
2 × 95
2 × 150
M12
M12
200
1GE33-8 . A3
2 × 120
4 × 240
M12
2 × 95
2 × 150
M12
M12
250
1GE35-0 . A3
2 × 185
4 × 240
M12
2 × 150
2 × 240
M12
M12
315
1GE36-1 . A3
2 × 240
4 × 240
M12
2 × 185
4 × 240
M12
M12
400
1GE37-5 . A3
3 × 185
4 × 240
M12
2 × 240
4 × 240
M12
M12
Cu busbar
450
1GE38-4 . A3
4 × 150
8 × 240
M12
3 × 185
4 × 240
M12
M12
Cu busbar
560
1GE41-0 . A3
4 × 185
8 × 240
M12
4 × 185
6 × 240
M12
M12
Cu busbar
500 ... 600 V 3 AC
110
1GF31-8 . A3
120
4 × 240
M12
95
2 × 150
M12
M12
132
1GF32-2 . A3
2 × 70
4 × 240
M12
120
2 × 150
M12
M12
160
1GF32-6 . A3
2 × 95
4 × 240
M12
2 × 70
2 × 185
M12
M12
200
1GF33-3 . A3
2 × 120
4 × 240
M12
2 × 95
2 × 240
M12
M12
250
1GF34-1 . A3
2 × 185
4 × 240
M12
2 × 120
4 × 240
M12
M12
315
1GF34-7 . A3
2 × 185
4 × 240
M12
2 × 150
4 × 240
M12
M12
400
1GF35-8 . A3
2 × 240
4 × 240
M12
2 × 185
4 × 240
M12
M12
500
1GF37-4 . A3
3 × 185
8 × 240
M12
2 × 240
6 × 240
M12
M12
Cu busbar
560
1GF38-1 . A3
4 × 150
8 × 240
M12
3 × 185
6 × 240
M12
M12
Cu busbar
660 ... 690 V 3 AC
75
1GH28-5 . A3
50
4 × 240
M12
35
2 × 70
M12
M12
90
1GH31-0 . A3
50
4 × 240
M12
50
2 × 150
M12
M12
110
1GH31-2 . A3
70
4 × 240
M12
70
2 × 150
M12
M12
132
1GH31-5 . A3
95
4 × 240
M12
70
2 × 150
M12
M12
160
1GH31-8 . A3
120
4 × 240
M12
95
2 × 150
M12
M12
200
1GH32-2 . A3
2 × 70
4 × 240
M12
120
2 × 150
M12
M12
250
1GH32-6 . A3
2 × 95
4 × 240
M12
2 × 70
2 × 185
M12
M12
315
1GH33-3 . A3
2 × 120
4 × 240
M12
2 × 95
2 × 240
M12
M12
400
1GH34-1 . A3
2 × 185
4 × 240
M12
2 × 120
4 × 240
M12
M12
450
1GH34-7 . A3
2 × 185
4 × 240
M12
2 × 150
4 × 240
M12
M12
560
1GH35-8 . A3
2 × 240
4 × 240
M12
2 × 185
4 × 240
M12
M12
710
1GH37-4 . A3
3 × 185
8 × 240
M12
3 × 150
6 × 240
M12
M12
Cu busbar
800
1GH38-1 . A3
4 × 150
8 × 240
M12
3 × 185
6 × 240
M12
M12
Cu busbar
1)
The recommendations for the North American market in AWG or MCM
must be taken from the appropriate NEC (National Electrical Code) and
CEC (Canadian Electrical Code) standards.
© Siemens AG 2015