SIEMENS
4/38
Siemens D 11 · 2015
■
Characteristic curves
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
Current derating depending on the pulse frequency
To reduce motor noise or to increase output frequency, the
pulse frequency can be increased relative to the factory setting
(1.25 kHz or 2 kHz). When the pulse frequency is increased, the
derating factor of the output current must be taken into account.
This derating factor must be applied to the currents specified in
the technical specifications.
For further information, please refer to the SINAMICS Low
Voltage Engineering Manual.
Derating factor of the output current depending on the pulse frequency for devices with a rated pulse frequency of 2 kHz
Derating factor of the output current depending on the pulse frequency for devices with a rated pulse frequency of 1.25 kHz
SINAMICS G150
Type rating
Output current
at 2 kHz
Derating factor
for pulse frequency
6SL3710-...
kW
A
2.5 kHz
4 kHz
380 ... 480 V 3 AC
1GE32-1 . A3
110
210
95 %
82 %
1GE32-6 . A3
132
260
95 %
83 %
1GE33-1 . A3
160
310
97 %
88 %
1GE33-8 . A3
200
380
96 %
87 %
1GE35-0 . A3
250
490
94 %
78 %
SINAMICS G150
Type rating
Output current
at 1.25 kHz
Derating factor
for pulse frequency
6SL3710-...
kW
A
2 kHz
2.5 kHz
4 kHz
380 ... 480 V 3 AC
1GE36-1 . A3
315
605
83 %
72 %
64 %
1GE37-5 . A3
400
745
83 %
72 %
64 %
1GE38-4 . A3
450
840
87 %
79 %
64 %
1GE41-0 . A3
560
985
92 %
87 %
70 %
2GE41-1AA3
630
1120
83 %
72 %
64 %
2GE41-4AA3
710
1380
83 %
72 %
64 %
2GE41-6AA3
900
1560
87 %
79 %
64 %
500 ... 600 V 3 AC
1GF31-8 . A3
110
175
92 %
87 %
70 %
1GF32-2 . A3
132
215
92 %
87 %
70 %
1GF32-6 . A3
160
260
92 %
88 %
71 %
1GF33-3 . A3
200
330
89 %
82 %
65 %
1GF34-1 . A3
250
410
89 %
82 %
65 %
1GF34-7 . A3
315
465
92 %
87 %
67 %
1GF35-8 . A3
400
575
91 %
85 %
64 %
1GF37-4 . A3
500
735
87 %
79 %
64 %
1GF38-1 . A3
560
810
83 %
72 %
61 %
2GF38-6AA3
630
860
92 %
87 %
67 %
2GF41-1AA3
710
1070
91 %
85 %
64 %
2GF41-4AA3
1000
1360
87 %
79 %
64 %
© Siemens AG 2015