SIEMENS
4/36
Siemens D 11 · 2015
■
Technical specifications
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
SINAMICS G150 converter cabinet units, version A
6SL3710-2GH..-
....
Parallel connection
41-1AA3
41-4AA3
41-5AA3
41-8EA3
42-0EA3
42-2EA3
42-4E A3
42-7E A3
Line voltage
660 ... 690 V 3 AC
Type rating
• For
I
L
1)
kW
1000
1350
1500
1750
1950
2150
2400
2700
• For
I
H
1)
kW
900
1200
1350
1500
1750
1950
2150
2400
• For
I
L
at 60 Hz 460 V
or 575 V
2)
hp
–
–
–
–
–
–
–
–
• For
I
H
at 60 Hz 460 V
or 575 V
2)
hp
–
–
–
–
–
–
–
–
Output current
• Rated current
I
n
3)
A
1070
1360
1500
1729
1948
2158
2413
2752
• Base-load current
I
L
3) 4)
A
1036
1314
1462
1720
1940
2150
2390
2685
• Base-load current
I
H
3) 5)
A
950
1216
1340
1547
1742
1930
2158
2463
Input current
• Rated input current
3) 6)
A
1116
1424
1568
1800
2030
2245
2510
2865
• Input current, max.
A
1708
2186
2406
2765
3115
3450
3860
4400
• Current requirement, 24 V DC
auxiliary power supply
7)
A
2.8
2.8
3
4.7
4.7
4.7
4.7
6
Rated short-circuit current
according to IEC
8)
kA
2 × 65
2 × 84
2 × 84
2 × 85
2 × 85
2 × 85
2 × 85
2 × 85
Minimum
short-circuit current
9)
A
2 × 8400
2 × 10500
2 × 1800
2 × 1800
2 × 2000
2 × 2300
2 × 2500
2 × 3000
Power loss, max.
10)
at 50 Hz 690 V
kW
21.3
26.6
29
35
38
40
46
52
Cooling air requirement
m
3
/s
1.56
2.96
2.96
3.67
3.67
3.67
3.67
5.15
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
75/78
75/78
75/78
75/78
75/78
75/78
75/78
75/78
Cable lengths
between converter and motor
11)
• Shielded
m
300
300
300
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
450
450
450
Dimensions
• Width
12)
mm
2400
3200
3200
3600
3600
3600
3600
4400
• Height
13)
mm
2000
2000
2000
2000
2000
2000
2000
2000
• Depth
mm
600
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20,
without options)
kg
1700
2620
2700
3010
3010
3070
3860
4580
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 400 V, 500 V or 690 V.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 60 Hz 460 V or 575 V.
3)
The currents listed here are the aggregate current of the two converter
sections.
4)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or 150%
for 10 s with a load cycle duration of 300 s.
See Characteristic curves,
Section Overload capability.
5)
The base-load current
I
H
is based on a duty cycle of 150% for 60 s or
160% for 10 s with a duty cycle duration of 300 s.
See Characteristic
curves, Section Overload capability.
6)
The currents listed here are based on the rated output current.
7)
If the drive control is to remain active after a main infeed failure, the converter
must be externally supplied with 24 V DC.
The following must also be taken into account:
– CU320-2: 1 A
– TM31: 0.5 A
– AOP30: 0.2 A
– SMC: 0.6 A
– Current requirement of digital inputs/outputs.
8)
In conjunction with the specified fuses or circuit breakers.
9)
Minimum current required for reliably triggering the protective devices.
10)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating conditions.
11)
Longer cable lengths for specific configurations are available on request.
12)
Power units connected in parallel are shipped as two transport units.
13)
Version A:
The cabinet height increases by
– 250 mm for degree of protection IP21
– 400 mm for degrees of protection IP23, IP43 and IP54
– 405 mm for options
M13
and
M78
© Siemens AG 2015