SIEMENS
4/32
Siemens D 11 · 2015
■
Technical specifications
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
Line voltage
500 ... 600 V 3 AC
SINAMICS G150 converter cabinet units
6SL3710-1GF..-
....
Single connection
31-8.A3
32-2.A3
32-6.A3
33-3.A3
34-1.A3
34-7.A3
35-8.A3
37-4.A3
38-1.A3
Type rating
• For
I
L
at 50 Hz 500 V
1)
kW
110
132
160
200
250
315
400
500
560
• For
I
H
at 50 Hz 500 V
1)
kW
90
110
132
160
200
250
315
450
500
• For
I
L
at 60 Hz 575 V
2)
hp
150
200
250
300
400
450
600
700
800
• For
I
H
at 60 Hz 575 V
2)
hp
150
200
200
250
350
450
500
700
700
Output current
• Rated current
I
n
A
175
215
260
330
410
465
575
735
810
• Base-load current
I
L
3)
A
171
208
250
320
400
452
560
710
790
• Base-load current
I
H
4)
A
157
192
233
280
367
416
514
657
724
Input current
• Rated input current
5)
A
191
224
270
343
426
483
598
764
842
• Input current, max.
A
279
341
410
525
655
740
918
1164
1295
• Current requirement, 24 V DC
auxiliary power supply
6)
A
1.35
1.35
1.35
1.4
1.4
1.4
1.4
1.5
1.5
Rated short-circuit current
according to IEC
7)
kA
65
65
65
65
65
65
65
84
84
Minimum short-circuit
current
8)
A
2400
3000
3600
5200
5200
6200
8400
10500
10400/1800
9)
Power loss, max.
10)
• At 50 Hz 500 V
kW
3.8
4.2
5
6.1
8.1
7.8
8.7
12.7
14.1
• At 60 Hz 575 V
kW
3.2
3.6
4.1
5.1
6.7
7.5
8.4
12.5
13.8
Cooling air requirement
m
3
/s
0.36
0.36
0.36
0.36
0.78
0.78
0.78
1.48
1.48
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
69/73
69/73
69/73
69/73
72/75
72/75
72/75
72/75
72/75
Cable lengths
between converter and motor
11)
• Shielded
m
300
300
300
300
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
450
450
450
450
Dimensions
• Width for
version A/C
mm
800/400
800/400
800/400
800/400
1200/600
1200/600
1200/600
1600/1000
1600/1000
• Height
12)
mm
2000
2000
2000
2000
2000
2000
2000
2000
2000
• Depth
mm
600
600
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20,
without options) for version A/C
kg
460/300
460/300
460/300
460/300
750/670
750/670
860/670
1150/940
1150/960
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 400 V.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 60 Hz 460 V.
3)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or
150% for 10 s with a load cycle duration of 300 s.
See Characteristic
curves, Section Overload capability.
4)
The base-load current
I
H
is based on a duty cycle of 150% for 60 s or
160% for 10 s with a duty cycle duration of 300 s.
See Characteristic
curves, Section Overload capability.
5)
The currents listed here are based on the rated output current.
6)
If the drive control is to remain active after a main infeed failure, the converter
must be externally supplied with 24 V DC.
The following must also be taken into account:
– CU320-2: 1 A
– TM31: 0.5 A
– AOP30: 0.2 A
– SMC: 0.6 A
– Current requirement of digital inputs/outputs.
7)
In conjunction with the specified fuses or circuit breakers.
8)
Minimum current required for reliably triggering the protective devices.
9)
For option
L26
(version A) the low value applies.
10)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating conditions.
11)
Longer cable lengths for specific configurations are available on request.
12)
Version A:
The cabinet height increases by
– 250 mm for degree of protection IP21
– 400 mm for degrees of protection IP23, IP43 and IP54
– 405 mm for options
M13
and
M78
Version C:
The cabinet height increases by
– 250 mm for degree of protection IP21
– 400 mm for degrees of protection IP23, IP43 and IP54
© Siemens AG 2015