SIEMENS
4/31
Siemens D 11 · 2015
■
Technical specifications
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
Technical specifications for single connection
Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
Line voltage
380 ... 480 V 3 AC
SINAMICS G150 converter cabinet units
6SL3710-1GE..-
....
Single connection
32-1.A3
32-6.A3
33-1.A3
33-8.A3
35-0.A3
36-1.A3
37-5.A3
38-4.A3
41-0.A3
Type rating
• For
I
L
at 50 Hz 400 V
1)
kW
110
132
160
200
250
315
400
450
560
• For
I
H
at 50 Hz 400 V
1)
kW
90
110
132
160
200
250
315
400
450
• For
I
L
at 60 Hz 460 V
2)
hp
150
200
250
300
400
500
600
600
800
• For
I
H
at 60 Hz 460 V
2)
hp
125
150
200
250
350
350
450
500
700
Output current
• Rated current
I
n
A
210
260
310
380
490
605
745
840
985
• Base-load current
I
L
3)
A
205
250
302
370
477
590
725
820
960
• Base-load current
I
H
4)
A
178
233
277
340
438
460
570
700
860
Input current
• Rated input current
5)
A
229
284
338
395
509
629
775
873
1024
• Input current, max.
A
335
410
495
606
781
967
1188
1344
1573
• Current requirement,
24 V DC auxiliary
power supply
6)
A
1.1
1.1
1.35
1.35
1.35
1.4
1.4
1.4
1.5
Rated short-circuit
current
according to IEC
7)
kA
65
65
65
65
65
65
65
84
84
Minimum short-circuit
current
8)
A
3000
3600
4400
4400
8000
10000
10500
16000/1800
9)
18400/2000
9)
Power loss, max.
10)
• At 50 Hz 400 V
kW
2.9
3.8
4.4
5.3
6.4
8.2
9.6
10.1
14.4
• At 60 Hz 460 V
kW
2.54
3.36
4.07
4.67
5.96
8.3
9.7
10.2
14.7
Cooling air requirement
m
3
/s
0.17
0.23
0.36
0.36
0.36
0.78
0.78
0.78
1.48
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
67/68
69/73
69/73
69/73
69/73
70/73
70/73
70/73
72/75
Cable lengths
between converter and
motor
11)
• Shielded
m
300
300
300
300
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
450
450
450
450
Dimensions
• Width for
version A/C
mm
800/400
800/400
800/400
1000/400
1000/400
1200/600
1200/600
1200/600
1600/1000
• Height
12)
mm
2000
2000
2000
2000
2000
2000
2000
2000
2000
• Depth
mm
600
600
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20,
without options) for
version A/C
kg
460/225
460/225
670/300
670/300
670/300
750/670
750/670
780/670
1100/880
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 400 V.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 60 Hz 460 V.
3)
The base-load current
I
L
is based on a load cycle of 110% for 60 s or
150% for 10 s with a load cycle duration of 300 s.
See Characteristic
curves, Section Overload capability.
4)
The base-load current
I
H
is based on a duty cycle of 150% for 60 s or
160% for 10 s with a duty cycle duration of 300 s.
See Characteristic
curves, Section Overload capability.
5)
The currents listed here are based on the rated output current.
6)
If the drive control is to remain active after a main infeed failure, the converter
must be externally supplied with 24 V DC.
The following must also be taken into account:
– CU320-2: 1 A
– TM31: 0.5 A
– AOP30: 0.2 A
– SMC: 0.6 A
– Current requirement of digital inputs/outputs.
7)
In conjunction with the specified fuses or circuit breakers.
8)
Minimum current required for reliably triggering the protective devices.
9)
For option
L26
(version A) the low value applies.
10)
The specified power losses are the maximum values for a utilization of
100%. The values are lower under normal operating conditions.
11)
Longer cable lengths for specific configurations are available on request.
12)
Version A:
The cabinet height increases by
– 250 mm for degree of protection IP21
– 400 mm for degrees of protection IP23, IP43 and IP54
– 405 mm for options
M13
and
M78
Version C:
The cabinet height increases by
– 250 mm for degree of protection IP21
– 400 mm for degrees of protection IP23, IP43 and IP54
© Siemens AG 2015