SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
L50
Cabinet lighting with service socket
With option
L50
, cabinet lighting is included with an additional
service socket for a SCHUKO connector (connector type F)
according to CEE 7/4. The power supply for the cabinet lighting
and the service socket is external and must be fuse-protected
for max. 10 A.
The cabinet lighting consists of an LED hand lamp with On/Off
switch and with magnetic fasteners on an approx. 3 m long con-
necting cable. The lamp is factory-positioned in the cabinet door
at a defined marking, and the connecting cable is wound on the
associated mount.
L55
Anti-condensation heating for cabinet
The anti-condensation heating is recommended at low ambient
temperatures and high levels of humidity to prevent condensa-
tion. A 100 W cabinet heater is installed in each cabinet section
(two heaters are installed per cabinet with cabinet section widths
of between 800 mm and 1200 mm).
The power supply for the anti-condensation heating (110 V to
230 V AC, at terminal block -X240) must be provided externally
and fused with max. 16 A.
L57
EMERGENCY OFF Category 0, 230 V AC or 24 V DC
EMERGENCY OFF Category 0 for uncontrolled stopping
according to EN 60204-1.
The function includes interrupting the power supply for the con-
verter via the line contactor and bypassing the microprocessor
controller using a safety combination according to EN 60204-1.
The motor coasts to a standstill. When delivered, the pushbutton
circuit is preset to 230 V AC. Jumpers must be appropriately set
when using 24 V DC.
Notice:
Option
L57
always requires electrical separation from the line
supply, this means for converters in a single circuit, for converter
currents
≤
800 A, option
L13
and for converter currents > 800 A,
option
L26
. For converters with power units connected in paral-
lel, electrical separation from the line supply is included as stan-
dard.
L59
EMERGENCY STOP Category 1, 230 V AC
EMERGENCY STOP Category 1 for controlled stopping accord-
ing to EN 60204-1.
The function stops the drive using a fast stop along a down ramp
that is parameterized by the user. The power supply to the con-
verter is then interrupted as described for EMERGENCY OFF
Category 0.
In order to maintain the specified stopping times, it may be
necessary to use a braking unit.
Notice:
Option
L59
always requires electrical separation from the line
supply, this means for converters in a single circuit, for converter
currents
≤
800 A, option
L13
and for converter currents > 800 A,
option
L26
. For converters with power units connected in paral-
lel, electrical separation from the line supply is included as stan-
dard.
L60
EMERGENCY STOP Category 1, 24 V DC
EMERGENCY STOP Category 1 for controlled stopping accord-
ing to EN 60204-1.
The function stops the drive using a fast stop along a down ramp
that is parameterized by the user. The power supply to the con-
verter is then interrupted as described for EMERGENCY OFF
Category 0.
In order to maintain the specified stopping times, it may be nec-
essary to use a braking unit.
Notice:
Option
L60
always requires electrical separation from the line
supply, this means for converters in a single circuit, for converter
currents
≤
800 A, option
L13
and for converter currents > 800 A,
option
L26
. For converters with power units connected in paral-
lel, electrical separation from the line supply is included as stan-
dard.
Terminal
-X240:
Meaning
1
L1 (110 ... 230 V AC)
2
N
3
PE
Terminal
-X120:
Meaning
7
Loop in the EMERGENCY OFF pushbutton from the plant side;
remove jumper 7-8!
8
Loop in the EMERGENCY OFF pushbutton from the plant side;
remove jumper 7-8!
15
"On" for monitored start; remove jumper 15-16!
16
"On" for monitored start; remove jumper 15-16!
17
Checkback signal, "Safety combination has tripped"
18
Checkback signal, "Safety combination has tripped"
Terminal
-X120:
Meaning
7
Loop in the EMERGENCY OFF pushbutton from the plant side;
remove jumper 7-8!
8
Loop in the EMERGENCY OFF pushbutton from the plant side;
remove jumper 7-8!
15
"On" for manual start; remove jumper 15-16!
16
"On" for manual start; remove jumper 15-16!
17
Checkback signal, "Safety combination has tripped"
18
Checkback signal, "Safety combination has tripped"
Terminal
-X120:
Meaning
7
Loop in the EMERGENCY OFF pushbutton from the plant side;
remove jumper 7-8!
8
Loop in the EMERGENCY OFF pushbutton from the plant side;
remove jumper 7-8!
15
"On" for manual start; remove jumper 15-16!
16
"On" for manual start; remove jumper 15-16!
17
Checkback signal, "Safety combination has tripped"
18
Checkback signal, "Safety combination has tripped"