SIEMENS
4/18
Siemens D 11 · 2015
■
Options
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
G51
TM150 temperature sensor evaluation unit
The TM150 Terminal Module is a DRIVE-CLiQ component that is
used to acquire and evaluate data from several temperature
sensors. The temperature is measured in a temperature range
from -99° C to +250° C for the following temperature sensors:
•
Pt100 (with monitoring for wire breakage and short-circuit)
•
Pt1000 (with monitoring for wire breakage and short-circuit)
•
KTY84 (with monitoring for wire breakage and short-circuit)
•
PTC (with monitoring for short-circuit)
•
Bimetallic NC contact (without monitoring)
For the temperature sensor inputs, for each terminal block the
evaluation can be parameterized for 1 × 2-wire, 2 × 2-wire,
3-wire or 4-wire. There is no galvanic isolation in the TM150
Terminal Module.
A maximum of 12 temperature sensors can be connected to the
TM150 Terminal Module.
For a description of the TM150 Terminal Module, see
SINAMICS G130 converter built-in units, Supplementary system
components.
G60
TM31 Terminal Module
The TM31 Terminal Module is used to extend the customer ter-
minals on the CU320-2 Control Unit.
The following additional interfaces are available:
•
8 digital inputs
•
4 bidirectional digital inputs/outputs
•
2 relay outputs with changeover contact
•
2 analog inputs
•
2 analog outputs
•
1 temperature sensor input (KTY84-130/PTC)
•
2 DRIVE-CLiQ sockets
•
1 connection for the electronics power supply via the 24 V DC
supply connector
•
1 PE connection
To simplify configuration and commissioning of the drive, the op-
tional TM31 Terminal Module can already be preset to a variety
of factory settings, which can then be selected during commis-
sioning.
For further information, please refer to the SINAMICS Low
Voltage Engineering Manual.
For a description of the TM31 Terminal Module, see
SINAMICS G130 converter built-in units, Supplementary system
components.
G61
Additional TM31 Terminal Module
With option
G61
, the number of digital inputs/outputs, as well as
the number of analog inputs/outputs in the drive system can be
expanded using a second TM31 Terminal Module (in addition to
the TM31 Terminal Module that can be selected using option
G60
).
Note:
Option
G61
requires option
G60
.
For a description of the TM31 Terminal Module, see
SINAMICS G130 converter built-in units, Supplementary system
components.
G62
TB30 Terminal Board
The TB30 Terminal Board is inserted into the option slot of the
Control Unit and offers the possibility of expanding the CU320-2
Control Unit by four digital inputs/outputs each as well as two
analog inputs/outputs each.
Note:
Option
G62
cannot be combined with options
G20
(CBC10
communication board) or
G33
(CBE20 communication board).
For a description of the TB30 Terminal Board, see
SINAMICS G130 converter built-in units, Supplementary system
components.
K01
Safety license for one axis
The Safety Integrated basic functions do not require a license.
However, the Safety Integrated extended functions require a li-
cense for each axis equipped with safety functions. It is irrele-
vant which safety functions are used and how many. Option
K01
contains the license for one axis.
Subsequent licensing is possible in the Internet via the
WEB License Manager by generating a license key:
/automation/license
K50
SMC30 Sensor Module Cabinet-Mounted
The SMC30 Sensor Module Cabinet-Mounted can be used to
evaluate the encoders of motors without a DRIVE-CLiQ inter-
face. External encoders can also be connected via the SMC30.
The following encoder signals can be evaluated:
•
Incremental encoders TTL/HTL with and without wire break
detection (wire break detection is only available with bipolar
signals)
•
SSI encoders with TTL/HTL incremental signals
•
SSI encoders without incremental signals
The motor temperature can also be measured using KTY84-130
or PTC thermistors.
For a description of the SMC30 Sensor Module Cabinet-
Mounted, see SINAMICS G130 converter built-in units, Supple-
mentary system components.
K51
VSM10 Voltage Sensing Module Cabinet-Mounted
The VSM10 Voltage Sensing Module is used to measure the volt-
age characteristic on the motor side, so that the following func-
tion can be implemented:
•
Operation of a permanent-magnet synchronous motor without
encoder with the requirement to be able to connect to a motor
that is already running (flying restart function).
•
Quick flying restart of large induction motors: The time for the
demagnetization of the motor is eliminated through the
measurement of the voltage.
For a description of the VSM10 Voltage Sensing Module
Cabinet-Mounted, see SINAMICS G130 converter built-in units,
Supplementary system components.
K52
Second SMC30 Sensor Module Cabinet-Mounted
With option
K50
, the converter cabinet contains an SMC30 Sen-
sor Module Cabinet-Mounted. An additional SMC30 Sensor
Module enables reliable actual-value acquisition when using
Safety Integrated extended functions (requires a license: Option
K01
).
© Siemens AG 2015