SIEMENS
4/13
Siemens D 11 · 2015
■
Options
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
Option selection matrix
Certain options are mutually exclusive. The tables below only
provide an overview. Please refer to the descriptions of the indi-
vidual options for a precise description of the options and other
exclusions.
Electrical options
G20
G33
G51
G61
G62
K50
K51
K87
L00
L01
L13
L22
L23
L26
L57
L59
L60
L61
L62
L86
L87
G20
–
–
G33
–
–
G51
–
G61
4)
G62
–
–
K50
–
K51
–
K87
4)
L00
–
1)
–
L01
–
–
L13
2)
3)
3)
3)
L22
–
–
–
L23
1)
–
–
L26
2)
3)
3)
3)
L57
3)
3)
–
–
L59
3)
3)
–
–
L60
3)
3)
–
–
L61
–
L62
–
L86
–
L87
–
Option can be ordered
–
Option cannot be ordered
1)
For converters
≤
500 kW / 700 hp, the line reactor (order code
L23
) is
included in the converter scope of delivery. For converters > 500 kW /
700 hp, option
L23
must be ordered separately when the converter is to be
operated on line supplies with high short-circuit power (R
SC
> 20) or when
a line filter is used (option
L00
).
2)
Combination
L13/L26
only possible for currents < 800 A. As of 800 A,
circuit breakers are used that also include the function of options
L13
and
L26
.
3)
Options
L57
,
L59
and
L60
always require electrical separation from the
line supply, this means for converters in a single circuit, for converter cur-
rents
≤
800 A, option
L13
and for converter currents > 800 A, option
L26
.
For converters with power units connected in parallel, electrical separation
from the line supply is included as standard.
4)
A combination of options
G61
and
K87
as a special version is available on
request.
© Siemens AG 2015