SIEMENS
4/6
Siemens D 11 · 2015
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
■
Function
AOP30 Advanced Operator Panel
An AOP30 Advanced Operator Panel is located in the cabinet
door of the converter for the operator control and monitoring as
well as for the commissioning.
The AOP30's two-stage safety concept prevents unintentional or
unauthorized changes to settings. Operation of the drive from
the operator panel can be disabled by the keyboard lock so that
only parameter values and process variables can be displayed
on the operator panel. The OFF key is factory-set to "active", but
can be deactivated by the customer. A password can be used
to prevent the unauthorized changing of converter parameters.
The user is guided by interactive menus through the drive com-
missioning screens. When commissioning the drive for the first
time, only six motor parameters (which can be found on the mo-
tor rating plate) have to be entered on the AOP30. The closed-
loop control is then optimized automatically to adapt the con-
verter to the motor.
German
,
English
,
French
,
Italian
,
Spanish
and
Chinese
are
stored on the CU320-2 Control Unit CompactFlash card as oper-
ator panel languages. The desired language must be down-
loaded to the AOP30 prior to commissioning. In addition to these
preinstalled languages,
Russian
and
Portuguese
(Brazil) are
also available for subsequent installation. Further languages are
available on request.
Examples of plain-text displays during various phases of opera-
tion are shown below.
The
first commissioning
is performed via the operator panel.
Only six motor parameters have to be entered:
Power, speed, current, cos
ϕ
, voltage and frequency of the
motor.
This information can be found on the motor rating plate, and
must be entered in the screens on the display by following a
short, menu-assisted procedure. The motor cooling method
must also be specified.
The next screen contains the parameter values that are used to
automatically optimize the control.
During
operation
, the display shows current data, such as set-
points and actual values as absolute values or it is possible to
parameterize up to three process variables as a quasi-analog
bar display.
Any
alarms
which occur are signaled by the flashing of the
yellow "ALARM" LED,
faults
by the lighting up of the red "FAULT"
LED. There is also an indication of the cause displayed in plain
text on the display's status line.
Select
Back
G_D011_EN_00047b
Help
AOP
diagnosis
AOP
settings
Device commissioning
Drive commissioning
Service / Commissioning
Motor data
Back
p0304
MOT.U_rated
400.0 V
p0305
MOT. I_rated
405.0 A
p0307
MOT.P_rated
235.0 kW
p0308
MOT.CosPhi_ rated
0.870
Help
Change
OK
G_D011_EN_00048
Basic commissioning
Back
p0700
Default BI
S/G150
TM 31
p1000
Default DI n_set
TM 31
AIO
p1080
Minimum speed
0.000
rpm
p1082
Maximum speed
1500.000
rpm
Help
Change
Further
G_D011_EN_00049a
G_D011_EN_00011c
Vou
t
Imot
Nact
7
48
385.3 V
1450.0 rpm
kW
Nm
Hz
rpm
410
2700
48.50
1450.0
0
1450.0 rpm
Nact:
Pact
M
Fout
Nset
Operation
12:25:30
A
0%
50
100%
0%
50
100%
G_D011_EN_00012b
Operation
12:25:30
NSET
1465.50
rpm
Pact
410
kW
Fout
48.50
Hz
Vout
385.3
V
Imot
748 A
Nact
1465 rpm
G_D011_EN_00050a
(3 : Vector) Current fault in
F 07901 Motor overspeed
Help
Alt
Back
Ack.
Motor overspeed
Fault val = 000000007
00000007 (hex)
Cause:
The maximum permisible positive or
negative speed has been exceeded.
The maximum permissile positive speed
is calculated as follows:
Back
G_D011_EN_00051a
© Siemens AG 2015