SIEMENS
3/75
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Supplementary system components > SMC30 Sensor Module Cabinet-Mounted
■
Overview
SMC30 Sensor Module Cabinet-Mounted
The SMC30 Sensor Module Cabinet-Mounted is required to eval-
uate the encoder signals of motors without a DRIVE-CLiQ inter-
face. External encoders can also be connected via the SMC30.
The following encoder signals can be evaluated:
•
Incremental encoders TTL/HTL with/without open-circuit
detection (open-circuit detection is only available with bipolar
signals)
•
SSI encoder with TTL/HTL incremental signals
•
SSI encoder without incremental signals
The motor temperature can also be detected using KTY84-130
or PTC thermistors.
■
Design
The SMC30 Sensor Module Cabinet-Mounted features the fol-
lowing connections and interfaces as standard:
•
1 encoder connection including motor temperature detection
(KTY84-130 or PTC) via SUB-D connector or terminals
•
1 DRIVE-CLiQ interface
•
1 connection for the electronics power supply via the 24 V DC
supply connector
•
1 PE connection
The status of the SMC30 Sensor Module Cabinet-Mounted is
indicated using a multi-color LED.
The SMC30 Sensor Module Cabinet-Mounted can be snapped
onto a TH 35 mounting rail according to EN 60715 (IEC 60715).
The maximum encoder cable length between SMC30 modules
and encoders is 100 m. For HTL encoders, this length can be in-
creased to 300 m if the A+/A- and B+/B- signals are evaluated
and the power supply cable has a minimum cross-section of
0.5 mm
2
.
The signal cable shield can be connected to the SMC30 Sensor
Module Cabinet-Mounted via a shield connection terminal, e.g.
type SK8 from Phoenix Contact or type KLBÜ CO 1 from Weid-
müller. The shield connection terminal must not be used as a
strain relief mechanism.
■
Integration
SMC30 Sensor Modules Cabinet-Mounted communicate with a
Control Unit via DRIVE-CLiQ.
■
Selection and ordering data
For the SINAMICS S150 and SINAMICS S120 Cabinet Modules,
the SMC30 Sensor Module Cabinet-Mounted can be ordered as
an option by specifying order code
K50
.
■
Technical specifications
1)
Signal cables twisted in pairs and shielded.
Description
Article No.
SMC30 Sensor Module Cabinet-Mounted
Without DRIVE-CLiQ cable
6SL3055-0AA00-5CA2
SMC30 Sensor Module Cabinet-Mounted
6SL3055-0AA00-5CA2
Power requirement, max.
at 24 V DC,
without taking encoder into account
0.2 A
• Conductor cross-section, max.
2.5 mm
2
• Fuse protection, max.
20 A
Power loss, max.
10 W
Encoders which can be evaluated
• Incremental encoder
TTL/HTL
• SSI encoder with TTL/HTL
incremental signals
• SSI encoder without incre-
mental signals
• Input impedance
- TTL
570
Ω
-
HTL, max.
16 mA
• Encoder supply
24 V DC/0.35 A or 5 V DC/0.35
A
• Encoder frequency, max.
300 kHz
• SSI baud rate
100 ... 1000 kBaud
• Limiting frequency
300 kHz
• Resolution absolute position SSI
30 bit
• Cable length, max.
-
TTL encoder
100 m (328 ft) (only bipolar
signals permitted)
1)
-
HTL encoder
100 m (328 ft) for unipolar
signals
300 m (984 ft) for bipolar
signals
1)
-
SSI encoder
100 m (328 ft)
PE connection
M4 screw
Dimensions
• Width
30 mm (1.18 in)
• Height
150 mm (5.91 in)
• Depth
111 mm (4.37 in)
Weight, approx.
0.45 kg (1 lb)
Approvals, according to
cULus