SIEMENS
3/57
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Supplementary system components > AOP30 Advanced Operator Panel
■
Overview
The AOP30 Advanced Operator Panel is an input/output device
for converters of the SINAMICS series, preferably for cabinet in-
stallation.
It has the following characteristics:
•
Graphical backlit LCD display for plain text display and a bar
display of process variables
•
LEDs for display of the operating states
•
Help function describing causes of and remedies for faults
and alarms
•
Keypad for controlling drives during operation
•
Local/remote switchover for selecting the operating location
(control priority assigned to operator panel or customer
terminal block / communication channel)
•
Numeric keypad for input of setpoint or parameter values
•
Function keys for guided navigation in the menu
•
Two-stage safety strategy to protect against accidental or
unauthorized changes to settings.
- Operation of the drive from the operator panel can be
disabled by the keyboard lock so that only parameter values
and process variables can be displayed on the operator
panel.
-
A password can be used to prevent the unauthorized modifi-
cation of converter parameters.
•
Front panel with degree of protection IP55
The AOP30 and SINAMICS drive communicate via the RS232
serial interface with PPI protocol.
The AOP30 may be omitted if the drive is only operated via
PROFIBUS, for example, and no local display is required on the
cabinet. The AOP30 can then be used simply for commissioning
purposes and to obtain diagnostic information, in which case, it
is plugged into the RS232 interface on the CU320-2 Control Unit.
In this case, an external 24 V power supply (max. current
requirement 200 mA) is required.
Assignment of the serial plug-in cable
■
Design
The AOP30 is an operator panel with graphical display and
membrane keyboard. The device can be installed in a cabinet
door which is between 2 mm and 4 mm thick.
Features:
•
Display with green backlighting, resolution 240 × 64 pixels
•
Membrane keyboard with 26 keys
•
Connection for a 24 V power supply
•
RS232 interface
•
Time and date memory with internal battery backup
•
4 LEDs to indicate the operating state of the drive:
- RUN green
- ALARM yellow
- FAULT red
- Local/Remote green
■
Function
The current operating states, setpoints and actual values, pa-
rameters, indices, faults and alarms are displayed on the display
panel.
German, English, French, Italian, Spanish
and
Chinese
are
stored on the CU320-2 Control Unit CompactFlash card as oper-
ator panel languages. The desired language must be down-
loaded to the AOP30 prior to commissioning. In addition to these
preinstalled languages,
Russian
and
Portuguese
(Brazil) are
also available for subsequent installation. Further languages are
available on request.
2
3
5
5
3
2
RxD
TxD
M 0V
M 0V
TxD
RxD
9-pole SUB-D
9-pole SUB-D
AOP30
X540
CU320-2
X140
G_D011_EN_00068
© Siemens AG 2015