SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
■
Characteristic curves
Derating data
Pulse frequency
Rated power
1)
Rated output current in A
for a pulse frequency of
400 V
460 V
kW
hp
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.37
0.5
1.3
1.11
0.91
0.78
0.65
0.59
0.52
0.55
0.5
1.7
1.45
1.19
1.02
0.85
0.77
0.68
0.75
0.75
2.2
1.87
1.54
1.32
1.1
0.99
0.88
1.1
1
3.1
2.64
2.17
1.86
1.55
1.4
1.24
1.5
2
4.1
3.49
2.87
2.46
2.05
1.85
1.64
2.2
3
5.9
5.02
4.13
3.54
2.95
2.66
2.36
3
3
7.7
6.55
5.39
4.62
3.85
3.47
3.08
4
5
10.2
8.67
7.14
6.12
5.1
4.59
4.08
5.5
7.5
13.2
11.22
9.24
7.92
6.6
5.94
5.28
7.5
10
18
15.3
12.6
10.8
9
8.1
7.2
11
15
26
22.1
18.2
15.6
13
11.7
10.4
15
15
32
27.2
22.4
19.2
16
14.4
12.8
18.5
20
38
32.3
26.6
22.8
19
17.1
15.2
22
25
45
38.25
31.5
27
22.5
20.25
18
30
30
60
51
42
36
30
27
24
37
40
75
63.75
52.5
45
37.5
33.75
30
45
50
90
76.5
63
54
45
40.5
36
55
60
110
93.5
77
66
2)
55
2)
49.5
2)
44
2)
75
75
145
123.3
101.5
–
–
–
–
90
100
178
151.3
124.6
–
–
–
–
1)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
2)
Values apply only to IP20 variants.
© Siemens AG 2017