SIEMENS
4/23
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
Line voltage 380 ... 480 V 3 AC
PM230 Power Modules degree of protection IP20 standard variant
Without integrated line filter
6SL3210-1NE27-5UL0
6SL3210-1NE28-8UL0
6SL3210-1NE31-1UL0
6SL3210-1NE31-5UL0
With integrated line filter class A
6SL3210-1NE27-5AL0
6SL3210-1NE28-8AL0
6SL3210-1NE31-1AL0
6SL3210-1NE31-5AL0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
75
90
110
145
• Base-load current
I
L
1)
A
75
90
110
145
• Base-load current
I
H
2)
A
60
75
90
110
• Maximum current
I
max
A
90
112
135
165
Rated power
• Based on
I
L
kW
37
45
55
75
• Based on
I
H
kW
30
37
45
55
Rated pulse frequency
kHz
4
4
4
4
Efficiency
η
%
97
97
97
97
Power loss
3)
at rated current
kW
0.791
0.976
1.237
1.69
Cooling air requirement
m
3
/s (ft
3
/s)
0.08 (2.8)
0.08 (2.8)
0.15 (5.3)
0.15 (5.3)
Sound pressure level
L
pA
(1 m)
dB
<60
<60
<60
<60
24 V DC power supply
for Control Unit
A
1
1
1
1
Input current
4)
• Rated current
A
70
84
102
135
• Based on
I
H
A
56
70
84
102
Line supply connection
U1/L1, V1/L2, W1/L3
M6 screw studs
M6 screw studs
M8 screw studs
M8 screw studs
• Conductor cross-section
mm
2
25 ... 50
25 ... 50
35 ... 120
35 ... 120
Motor connection
U2, V2, W2
M6 screw studs
M6 screw studs
M8 screw studs
M8 screw studs
• Conductor cross-section
mm
2
25 ... 50
25 ... 50
35 ... 120
35 ... 120
Motor cable length, max.
5)
• Shielded
m (ft)
25 (82)
25 (82)
25 (82)
25 (82)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
275 (10.83)
275 (10.83)
350 (13.78)
350 (13.78)
• Height
-
Without integrated line filter
mm (in)
499 (19.65)
499 (19.65)
634 (24.96)
634 (24.96)
-
With integrated line filter
mm (in)
635 (25)
635 (25)
934 (36.77)
934 (36.77)
• Depth
-
Without operator panel
mm (in)
204 (8.03)
204 (8.03)
316 (12.44)
316 (12.44)
-
With operator panel, max.
mm (in)
275 (10.83)
275 (10.83)
387 (15.24)
387 (15.24)
Frame size
FSE
FSE
FSF
FSF
Weight, approx.
• Without integrated line filter
kg (lb)
15 (33.1)
15 (33.1)
34 (74.97)
34 (74.97)
• With integrated line filter
kg (lb)
22 (48.5)
22 (48.5)
46 (101.43)
46 (101.43)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find more information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules
with integrated line filter to maintain the limit values acc. to EN 61800-3
Category C2. With unshielded cables, Category C2 is not achieved.
© Siemens AG 2017