SIEMENS
4/22
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
Line voltage 380 ... 480 V 3 AC
PM230 Power Modules degree of protection IP20 standard variant
Without integrated line filter
6SL3210-
1NE22-6UG1
6SL3210-
1NE23-2UG1
6SL3210-
1NE23-8UG1
6SL3210-
1NE24-5UL0
6SL3210-
1NE26-0UL0
With integrated line filter class A
6SL3210-
1NE22-6AG1
6SL3210-
1NE23-2AG1
6SL3210-
1NE23-8AG1
6SL3210-
1NE24-5AL0
6SL3210-
1NE26-0AL0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
26
32
38
45
60
• Base-load current
I
L
1)
A
26
32
38
45
60
• Base-load current
I
H
2)
A
18
26
32
38
45
• Maximum current
I
max
A
39
52
64
57
67
Rated power
• Based on
I
L
kW
11
15
18.5
22
30
• Based on
I
H
kW
7.5
11
15
18.5
22
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency
η
%
97
97
98
98
97
Power loss
3)
at rated current
kW
0.291
0.355
0.423
0.539
0.726
Cooling air requirement
m
3
/s (ft
3
/s)
0.019 (0.7)
0.019 (0.7)
0.019 (0.7)
0.08 (2.8)
0.08 (2.8)
Sound pressure level
L
pA
(1 m)
dB
<65
<65
<65
<60
<60
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current
4)
• Rated current
A
27
33
39
42
56
• Based on
I
H
A
19
27
33
36
42
Line supply connection
U1/L1, V1/L2, W1/L3
Screw-type
terminals, plug-in
Screw-type
terminals, plug-in
Screw-type
terminals, plug-in
M6 screw studs
M6 screw studs
• Conductor cross-section
mm
2
6 ... 16
6 ... 16
6 ... 16
16 ... 35
16 ... 35
Motor connection
U2, V2, W2
Screw-type
terminals, plug-in
Screw-type
terminals, plug-in
Screw-type
terminals, plug-in
M6 screw studs
M6 screw studs
• Conductor cross-section
mm
2
6 ... 16
6 ... 16
6 ... 16
16 ... 35
16 ... 35
Motor cable length, max.
5)
• Shielded
m (ft)
25 (82)
25 (82)
25 (82)
25 (82)
25 (82)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
140 (5.51)
140 (5.51)
140 (5.51)
275 (10.83)
275 (10.83)
• Height
-
Without integrated line filter
mm (in)
355 (13.98)
355 (13.98)
355 (13.98)
419 (16.50)
419 (16.50)
-
With integrated line filter
mm (in)
355 (13.98)
355 (13.98)
355 (13.98)
512 (20.16)
512 (20.16)
• Depth
-
Without operator panel
mm (in)
165 (6.50)
165 (6.50)
165 (6.50)
204 (8.03)
204 (8.03)
-
With operator panel, max.
mm (in)
245 (9.65)
245 (9.65)
245 (9.65)
275 (10.83)
275 (10.83)
Frame size
FSC
FSC
FSC
FSD
FSD
Weight, approx.
• Without integrated line filter
kg (lb)
4.5 (9.92)
4.5 (9.92)
4.5 (9.92)
11 (24.3)
11 (24.3)
• With integrated line filter
kg (lb)
5.1 (11.25)
5.1 (11.25)
5.1 (11.25)
14 (30.87)
14 (30.87)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find more information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules
with integrated line filter to maintain the limit values acc. to EN 61800-3
Category C2. With unshielded cables, Category C2 is not achieved.
© Siemens AG 2017