SIEMENS
4/18
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
Line voltage 380 ... 480 V 3 AC
PM230 Power Modules, degree of protection IP55/UL Type 12
1)
With integrated line filter class A
6SL3223-
0DE31-1AG1
6SL3223-
0DE31-5AG1
6SL3223-
0DE31-8AG1
–
6SL3223-
0DE32-2AA0
6SL3223-
0DE33-0AA0
With integrated line filter class B
6SL3223-
0DE31-1BG1
6SL3223-
0DE31-5BG1
–
6SL3223-
0DE31-8BA0
6SL3223-
0DE32-2BA0
6SL3223-
0DE33-0BA0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
2)
A
26
32
38
38
45
60
• Base-load current
I
L
2)
A
26
32
38
38
45
60
• Base-load current
I
H
3)
A
18
26
32
32
38
45
• Maximum current
I
max
A
39
52
64
48
57
67
Rated power
• Based on
I
L
kW
11
15
18.5
18.5
22
30
• Based on
I
H
kW
7.5
11
15
15
18.5
22
Rated pulse frequency
kHz
4
4
4
4
4
4
Efficiency
η
%
97
97
98
97
97
97
Power loss
4)
at rated current
kW
0.299
0.365
0.435
0.478
0.569
0.784
Cooling air requirement
m
3
/s (ft
3
/s)
0.02 (0.7)
0.02 (0.7)
0.02 (0.7)
0.039 (1.4)
0.039 (1.4)
0.039 (1.4)
Sound pressure level
L
pA
(1 m)
dB
66.1
66.1
66.1
56
56
56
24 V DC power supply
for Control Unit
A
1
1
1
1
1
1
Input current
5)
• Rated current
A
27
33
39
39
42
56
• Based on
I
H
A
19
27
33
33
36
42
Line supply connection
U1/L1, V1/L2, W1/L3
Screw-type ter-
minals, plug-in
Screw-type ter-
minals, plug-in
Screw-type ter-
minals, plug-in
M6 screw studs
M6 screw studs
M6 screw studs
• Conductor cross-section
mm
2
6 ... 16
10 ... 16
10 ... 16
16 ... 35
16 ... 35
16 ... 35
Motor connection
U2, V2, W2
Screw-type ter-
minals, plug-in
Screw-type ter-
minals, plug-in
Screw-type ter-
minals, plug-in
M6 screw studs
M6 screw studs
M6 screw studs
• Conductor cross-section
mm
2
6 ... 16
10 ... 16
10 ... 16
16 ... 35
16 ... 35
16 ... 35
Motor cable length, max.
6)
• Shielded
m (ft)
25 (82)
25 (82)
25 (82)
25 (82)
25 (82)
25 (82)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
7)
IP55/UL Type 12
IP55/UL Type 12
IP55/UL Type 12
IP55
IP55
IP55
Dimensions
• Width
mm (in)
230 (9.06)
230 (9.06)
230 (9.06)
320 (12.60)
320 (12.60)
320 (12.60)
• Height
mm (in)
620 (24.41)
620 (24.41)
620 (24.41)
640 (25.20)
640 (25.20)
640 (25.20)
• Depth
-
Without operator panel
mm (in)
249 (9.80)
249 (9.80)
249 (9.80)
329 (12.95)
329 (12.95)
329 (12.95)
-
With operator panel, max.
mm (in)
266 (10.47)
266 (10.47)
266 (10.47)
346 (13.62)
346 (13.62)
346 (13.62)
Frame size
FSC
FSC
FSC
FSD
FSD
FSD
Weight, approx.
kg (lb)
9.5 (20.95)
9.5 (20.95)
9.5 (20.95)
31 (68.36)
31 (68.36)
31 (68.36)
1)
UL Type 12 only for frame size FSC
2)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
Typical values. You can find more information on the Internet at
5)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
6)
Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules
with integrated line filter to maintain the limit values of EN 61800-3
Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables,
Categories C2 and C1 are not achieved.
7)
It is essential to plug on an operator panel or the blanking cover in order to
achieve degree of protection IP54/IP55/UL Type 12.
For more information, see Operator panels and blanking cover for
PM230 Power Modules in section Supplementary system components.
© Siemens AG 2017