SIEMENS
4/13
Siemens D 35 · 2017
4
SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
■
Selection and ordering data
To ensure that a suitable Power Module is selected, the following
currents should be used for applications:
•
Rated output current for applications with low overload
(LO)
•
Base-load current for applications with high overload (HO)
With reference to the rated output current, the modules support
at least 2-pole to 6-pole low-voltage motors, e.g. the
SIMOTICS GP and SIMOTICS SD 1LE1 motor series. The rated
power is merely a guide value. For a description of the overload
performance, please refer to the general technical specifica-
tions of the Power Modules.
PM230 Power Modules degree of protection IP55/UL Type 12
It is essential to plug on an operator panel or the blanking
cover in order to achieve degree of protection IP54/IP55/
UL Type 12.
For more information, see Operator panels and Blanking cover
for PM230 Power Modules in section Supplementary system
components.
Note:
The power data in hp units are based on the NEC/CEC
standards for the North American market.
Rated power
1)
Rated output
current
I
rated
2)
Power based
on the base-load
current
3)
Base-load
current
I
H
3)
Frame size
PM230 Power Module
degree of protection IP55/
UL Type 12
4)
with
integrated
line filter class A
PM230 Power Module
degree of protection IP55/
UL Type 12
4)
with
integrated
line filter class B
400 V
460 V
400 V
460 V
kW
hp
A
kW
hp
A
Article No.
Article No.
380 ... 480 V 3 AC
0.37
0.5
1.3
0.25
0.33
0.9
FSA
6SL3223-0DE13-7AG1
6SL3223-0DE13-7BG1
0.55
0.5
1.7
0.37
0.33
1.3
FSA
6SL3223-0DE15-5AG1
6SL3223-0DE15-5BG1
0.75
0.75
2.2
0.55
0.5
1.7
FSA
6SL3223-0DE17-5AG1
6SL3223-0DE17-5BG1
1.1
1
3.1
0.75
0.75
2.2
FSA
6SL3223-0DE21-1AG1
6SL3223-0DE21-1BG1
1.5
2
4.1
1.1
1
3.1
FSA
6SL3223-0DE21-5AG1
6SL3223-0DE21-5BG1
2.2
3
5.9
1.5
1.5
4.1
FSA
6SL3223-0DE22-2AG1
6SL3223-0DE22-2BG1
3
3
7.7
2.2
3
5.9
FSA
6SL3223-0DE23-0AG1
6SL3223-0DE23-0BG1
4
5
10.2
3
3
7.7
FSB
6SL3223-0DE24-0AG1
6SL3223-0DE24-0BG1
5.5
7.5
13.2
4
5
10.2
FSB
6SL3223-0DE25-5AG1
6SL3223-0DE25-5BG1
7.5
10
18
5.5
5
13.2
FSB
6SL3223-0DE27-5AG1
6SL3223-0DE27-5BG1
11
15
26
7.5
10
18
FSC
6SL3223-0DE31-1AG1
6SL3223-0DE31-1BG1
15
15
32
11
15
26
FSC
6SL3223-0DE31-5AG1
6SL3223-0DE31-5BG1
18.5
20
38
15
15
32
FSC
6SL3223-0DE31-8AG1
–
FSD
–
6SL3223-0DE31-8BA0
22
25
45
18.5
20
38
FSD
6SL3223-0DE32-2AA0
6SL3223-0DE32-2BA0
30
30
60
22
25
45
FSD
6SL3223-0DE33-0AA0
6SL3223-0DE33-0BA0
37
40
75
30
30
60
FSE
6SL3223-0DE33-7AA0
6SL3223-0DE33-7BA0
45
50
90
37
40
75
FSE
6SL3223-0DE34-5AA0
6SL3223-0DE34-5BA0
55
60
110
45
50
90
FSF
6SL3223-0DE35-5AA0
6SL3223-0DE35-5BA0
75
75
145
55
60
110
FSF
6SL3223-0DE37-5AA0
6SL3223-0DE37-5BA0
90
100
178
75
75
145
FSF
6SL3223-0DE38-8AA0
6SL3223-0DE38-8BA0
1)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
2)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are valid for 400 V and are specified on the
rating plate of the Power Module.
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
UL Type 12 only for frame sizes FSA to FSC
© Siemens AG 2017