PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
Maximum permissible cable lengths from the motor to the inverter when using output reactors or filters depending on the
voltage range and the Power Module being used
The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result
in the following maximum cable lengths:
Maximum permissible motor cable lengths (shielded/unshielded) in m (ft)
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
PM230 Power Module degree of protection IP20
Available frame sizes
Without output reactor/sine-wave filter
25/100 (82/328)
25/100 (82/328)
25/100 (82/328)
25/100 (82/328)
25/100 (82/328)
25/100 (82/328)
With optional output reactor
• At 380 ... 415 V 3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
–
–
–
• At 440 ... 480 V 3 AC
100/150
(328/492)
100/150
(328/492)
100/150
(328/492)
–
–
–
• At 380 ... 480 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
With optional sine-wave filter
• At 380 ... 480 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
With integrated line filter class A
(EMC category C3)
• At 380 ... 480 V 3 AC
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
With optional external line filter class B
(EMC category C1
1)
, with unfiltered
Power Module, maintains the limit values
acc. to EN 61800-3)
• At 380 ... 480 V 3 AC
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
50/- (164/-)
With optional external line filter class B
and output reactor (EMC category C2
1)
,
with unfiltered Power Module, maintains
the limit values acc. to EN 61800-3)
• At 380 ... 415 V 3 AC
150/- (492/-)
150/- (492/-)
150/- (492/-)
–
–
–
• At 440 ... 480 V 3 AC
100/- (328/-)
100/- (328/-)
100/- (328/-)
–
–
–
1)