SIEMENS
3/24
Siemens D 35 · 2017
■
Overview
(continued)
3
System configuration
SINAMICS G120P and SINAMICS G120P Cabinet pump, fan, compressor converters
Integrated Drive Systems
SINAMICS G120P Power Modules for use in water/wastewater applications and in industrial environments,
with degree of protection IP20, 380 to 480 V 3 AC
SINAMICS G120P
Rated power
1)
Rated
output
current
I
rated
2)
Power based on the
base-load current
I
H
3)
Base-load
current
I
H
3)
Power Module
400 V
460 V
400 V
460 V
Frame size
Type
Without
integrated line
filter
With
integrated line filter
class A (Category C2)
kW
hp
A
kW
hp
A
Article No.
Article No.
22
25
45
18.5
20
38
FSD
PM240P-2
6SL3210-1RE24-5UL0
6SL3210-1RE24-5AL0
30
30
60
22
25
45
6SL3210-1RE26-0UL0
6SL3210-1RE26-0AL0
37
40
75
30
30
60
6SL3210-1RE27-5UL0
6SL3210-1RE27-5AL0
45
50
90
37
40
75
FSE
6SL3210-1RE28-8UL0
6SL3210-1RE28-8AL0
55
60
110
45
50
90
6SL3210-1RE31-1UL0
6SL3210-1RE31-1AL0
75
75
145
55
60
110
FSF
6SL3210-1RE31-5UL0
6SL3210-1RE31-5AL0
90
100
178
75
75
145
6SL3210-1RE31-8UL0
6SL3210-1RE31-8AL0
110
125
205
90
100
178
6SL3210-1RE32-1UL0
6SL3210-1RE32-1AL0
132
150
250
110
125
205
6SL3210-1RE32-5UL0
6SL3210-1RE32-5AL0
160
200
300
132
150
240
GX
PM330
6SL3310-1PE33-0AA0
–
200
250
370
160
200
296
6SL3310-1PE33-7AA0
–
250
300
460
200
200
368
6SL3310-1PE34-6AA0
–
315
400
585
250
300
468
HX
6SL3310-1PE35-8AA0
–
355
450
655
250
300
491
6SL3310-1PE36-6AA0
–
400
500
735
315
350
551
6SL3310-1PE37-4AA0
–
450
500
840
355
450
672
JX
6SL3310-1PE38-4AA0
–
500
600
910
400
500
728
6SL3310-1PE38-8AA0
–
560
700
1021
450
500
786
6SL3310-1PE41-0AA0
–
1)
PM240P-2
:
Rated power based on the rated output current
I
rated
. The
rated output current
I
rated
is based on the duty cycle for low overload
(LO). PM330
: Rated power based on the base-load current
I
L
. The
base-load current
I
L
is based on the duty cycle for low overload (LO)
.
2)
PM240P-2
:
The rated output current
I
rated
is based on the duty cycle
for low overload (LO). These current values are valid for 400 V and are
specified on the rating plate of the Power Module.
3)
The base-load current
I
H
is based on the duty cycle for
high overload (HO).
© Siemens AG 2017