Technical specifications
(continued)
3
System configuration
SINAMICS G120P and SINAMICS G120P Cabinet pump, fan, compressor converters
SINAMICS G120P and SINAMICS G120P Cabinet pump, fan, compressor converters
Power Modules
PM230
PM240P-2
PM330
Cabinet
Overload capability
• Low overload
(LO)
Note:
When the overload capability is used, the
base-load current
I
L
is not reduced.
FSA to FSC:
1.5 × base-load current
I
L
(i. e. 150 % overload) for
3 s
plus
1.1 × base-load current
I
L
(i. e. 110 % overload) for
57 s within a cycle time of
300 s
FSD to FSF:
1.1 × base-load current
I
L
(i.e. 110 % overload) for
60 s within a cycle time of
300 s
1.35 × base-load current
I
L
(i.e. 135 % overload) for
3 s
plus
1.1 × base-load current
I
L
(i.e. 110 % overload) for
57 s within a cycle time of
300 s
1.35 × base-load current
I
L
(i.e. 135 % overload) for
3 s
or
1.1 × base-load current
I
L
(i.e. 110 % overload) for
60 s within a cycle time of
300 s
1.35 × base-load current
I
L
(i.e. 135 % overload)
for 3 s
or
1.1 × base-load current
I
L
(i.e. 110 % overload) for
60 s within a cycle time of
300 s
• High overload
(HO)
Note:
When the overload capability is used, the
base-load current
I
H
is not reduced.
FSA to FSC:
2 × base-load current
I
H
(i. e. 200 % overload) for
3 s
plus
1.5 × base-load current
I
H
(i. e. 150 % overload) for
57 s within a cycle time of
300 s
FSD to FSF:
1.5 × base-load current
I
H
(i.e. 150 % overload) for
60 s within a cycle time of
300 s
1.5 × base-load current
I
H
(i. e. 150 % overload) for
60 s within a cycle time of
300 s
1.5 × base-load current
I
H
(i. e. 150 % overload) for
60 s within a cycle time of
300 s
1.5 × base-load current
I
H
(i. e. 150 % overload) for
60 s within a cycle time of
300 s
Possible braking methods
DC braking
DC braking
Compound braking
DC braking
Dynamic braking with
optional Braking Module
DC braking
Dynamic braking with
optional Braking Module
Overvoltage category acc. to IEC 61800-5-1
III
III
Supply circuits: III
Non-supply circuits: II
III
Degree of protection
IP55/UL Type 12 (with
BOP-2 or blanking cover)
IP54/UL Type 12
(with IOP)
IP20 (Standard or Push
Through)
IP20
IP20
Standard: IP20
Optional: IP21, IP23, IP43
and IP54
Cooling
Power units with
increased air cooling
using integrated fans
Internal ventilation, power
units with increased air
cooling by built-in fans
Internal ventilation, power
units with increased air
cooling by built-in fans
Internal ventilation, power
units with increased air
cooling by built-in fans
Protection functions
• Undervoltage
• Overvoltage
• Overcurrent/overload
• Overtemperature
• Ground fault
• Short-circuit
• Stall protection
• Motor blocking protection
• Motor overtemperature
• Parameter locking
Short-Circuit Current Rating SCCR
acc. to UL
(Short-Circuit Current Rating)
1)
Degree of protection IP55
frame sizes FSA to FSC:
40 kA
Degree of protection IP20:
65 kA
65 kA
100 kA
2)
–
Rated short-circuit current
acc. to IEC
2)
–
65 kA
100 kA
2)
65 kA
2)
1)
Applies to industrial control panel installations according to
NEC Article 409 or UL 508A/508C respectively UL 61800-5-1.
2)
In combination with the fuses specified in section Recommended line-side
power components.