Siemens D 35 · 2017
■
Technical specifications
(continued)
5
SINAMICS G120P Cabinet, converter cabinet units
SINAMICS G120P Cabinet, 75 kW to 630 kW
SINAMICS G120P Cabinet
Note:
The power data in hp units are based on the NEC/CEC stan-
dards for the North American market.
Information on the line connection, motor connection and
cabinet grounding can be found in section Cable cross-sections
and connections.
Line voltage 500 ... 690 V 3 AC
SINAMICS G120P Cabinet converter cabinet units
6SL3710-1PG35-8AA0-Z
6SL3710-1PG36-5AA0-Z
6SL3710-1PG37-2AA0-Z
Rated power
• At
I
L
690 V/50 Hz
1)
kW
500
560
630
• At
I
L
575 V/60 Hz
2)
hp
500
600
700
• At
I
H
690 V/50 Hz
1)
kW
450
500
560
• At
I
H
575 V/60 Hz
2)
hp
450
500
500
Output current
• Rated current
I
rated
(500 V ±10 %)
A
581
654
725
• Rated current
I
rated
(600 V ±10 %)
A
557
623
693
• Rated current
I
rated
(690 V ±10 %)
A
535
595
665
• Base-load current
I
L
(500 V ±10 %)
3)
A
569
640
710
• Base-load current
I
L
(690 V ±10 %)
3)
A
520
580
650
• Base-load current
I
H
(500 V ±10 %)
4)
A
482
523
580
• Base-load current
I
H
(690 V ±10 %)
4)
A
444
476
532
• Output current, max.
A
768
864
959
Input current
• Rated current
I
rated
(500 V ±10 %)
5)
A
596
679
753
• Rated current
I
rated
(600 V ±10 %)
5)
A
578
647
720
• Rated current
I
rated
(690 V ±10 %)
5)
A
555
618
690
• Base-load current
I
L
(500 V ±10 %)
3)
A
591
665
737
• Base-load current
I
L
(690 V ±10 %)
3)
A
540
602
675
• Base-load current
I
H
(500 V ±10 %)
4)
A
501
543
602
• Base-load current
I
H
(690 V ±10 %)
4)
A
461
494
552
• Input current, max.
A
798
897
995
Current requirement,
24 V DC auxiliary power supply
6)
A
1
1
1
Short-circuit current rating acc. to
IEC
in conjunction with the specified fuses
kA
65
65
65
Minimum short-circuit current
7)
• For 3NE1 fuses
A
10000
11000
13000
• For 3NA3 fuses
A
16000
20000
21000
Power loss, max.
at
I
rated
(500 V/40 °C), without options
kW
8.688
9.468
10.688
Coolant
Air
Air
Air
Coolant requirements
m
3
/s
(ft
3
/s)
0.7 (24.7)
0.7 (24.7)
0.7 (24.7)
Sound pressure level
L
pA
(1 m)
at 50/60 Hz
dB
69/69
69/69
69/69
Cable length, max.
between Power Module and motor
• When compliant with Categories C2
and C3 according to EN 61800-3
shielded
m (ft)
150 (492)
150 (492)
150 (492)
• When non-compliant with the limit
values for RI suppression and
without output reactor; unshielded
m (ft)
200 (656)
200 (656)
200 (656)
• When non-compliant with the limit
values for RI suppression with output
reactor; shielded/unshielded
m (ft)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
Dimensions
• Width
mm (in)
1200 (47.24)
9)
1200 (47.24)
9)
1200 (47.24)
9)
• Height
8)
mm (in)
2000 (78.74)
2000 (78.74)
2000 (78.74)
• Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
JX
JX
JX
Weight
(degree of protection IP20, w/o options)
kg (lb)
654 (1442)
697 (1537)
716 (1579)
1)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 690 V 3 AC/50 Hz.
2)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 575 V 3 AC/60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
135 % for 3 s with a duty cycle duration of 300 s
(see overload capability
characteristics)
.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s with a duty
cycle duration of 300 s
(see overload capability characteristics)
.
5)
The current values given here are based on the rated output current.
6)
If the drive closed-loop control is still to remain active when the main line sup-
ply fails, then the converter must be provided with an external 24 V DC supply.
7)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the trip-
ping time of the fuses is increased, which can lead to damage.
8)
The cabinet height increases by 300 mm (11.8 in) for degree of protection
IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and
IP54.
9)
The specified cabinet widths increase depending on the options selected.
For details, see description of option
L00
.