SIEMENS
5/25
Siemens D 35 · 2017
■
Technical specifications
(continued)
5
SINAMICS G120P Cabinet, converter cabinet units
SINAMICS G120P Cabinet, 75 kW to 630 kW
SINAMICS G120P Cabinet
Note:
The power data in hp units are based on the NEC/CEC stan-
dards for the North American market.
Information on the line connection, motor connection and
cabinet grounding can be found in section Cable cross-sections
and connections.
Line voltage 380 ... 480 V 3 AC
SINAMICS G120P Cabinet converter cabinet units
6SL3710-1PE38-4AA0-Z
6SL3710-1PE38-8AA0-Z
6SL3710-1PE41-0AA0-Z
Rated power
• At
I
L
400 V/50 Hz
1)
kW
450
500
560
• At
I
L
460 V/60 Hz
2)
hp
500
600
700
• At
I
H
400 V/50 Hz
1)
kW
355
400
450
• At
I
H
460 V/60 Hz
2)
hp
450
500
500
Output current
• Rated current
I
rated
(400 V ±10 %)
A
840
910
1021
• Rated current
I
rated
(480 V ±10 %)
A
677
739
847
• Base-load current
I
L
(400 V ±10 %)
3)
A
820
890
1000
• Base-load current
I
L
(480 V ±10 %)
3)
A
663
724
830
• Base-load current
I
H
(400 V ±10 %)
4)
A
672
728
786
• Base-load current
I
H
(480 V ±10 %)
4)
A
542
591
652
• Output current, max.
A
1107
1202
1350
Input current
• Rated current
I
rated
(400 V ±10 %)
5)
A
870
945
1061
• Rated current
I
rated
(480 V ±10 %)
5)
A
702
767
880
• Base-load current
I
L
(400 V ±10 %)
3)
A
850
925
1039
• Base-load current
I
L
(480 V ±10 %)
3)
A
687
751
862
• Base-load current
I
H
(400 V ±10 %)
4)
A
696
756
816
• Base-load current
I
H
(480 V ±10 %)
4)
A
561
614
677
• Input current, max.
A
1147
1248
1402
Current requirement,
24 V DC auxiliary power supply
6)
A
1
1
1
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses
without/with option L26
kA
65/65
65/65
65/65
Minimum short-circuit current
7)
• For 3NE1 fuses
A
10400
14000
16000
• For 3NA3 fuses
A
40000
40000
52000
Power loss, max.
at
I
rated
(400 V/40 °C), without options
kW
11.098
11.605
13.348
Coolant
Air
Air
Air
Coolant requirements
m
3
/s
(ft
3
/s)
0.7 (24.7)
0.7 (24.7)
0.7 (24.7)
Sound pressure level
L
pA
(1 m)
at 50/60 Hz
dB
69/69
69/69
69/69
Cable length, max.
between Power Module and motor
• When compliant with Categories C2
and C3 according to EN 61800-3
shielded
m (ft)
150 (492)
150 (492)
150 (492)
• When non-compliant with the limit
values for RI suppression and
without output reactor; unshielded
m (ft)
200 (656)
200 (656)
200 (656)
• When non-compliant with the limit
values for RI suppression with output
reactor; shielded/unshielded
m (ft)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
Dimensions
• Width
mm (in)
1200 (47.24)
9)
1200 (47.24)
9)
1200 (47.24)
9)
• Height
8)
mm (in)
2000 (78.74)
2000 (78.74)
2000 (78.74)
• Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
JX
JX
JX
Weight
(degree of protection IP20, w/o options)
kg (lb)
655 (1444)
676 (1490)
681 (1501)
1)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 400 V 3 AC/50 Hz.
2)
Rated power of a typ. 4-pole standard induction motor based on
base-load current
I
L
or
I
H
at 460 V 3 AC/60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
135 % for 3 s with a duty cycle duration of 300 s
(see overload capability
characteristics)
.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s with a
duty cycle duration of 300 s
(see overload capability characteristics)
.
5)
The current values given here are based on the rated output current.
6)
If the drive closed-loop control is still to remain active when the main line
supply fails, then the converter must be provided with an external 24 V DC
supply.
7)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
8)
The cabinet height increases by 300 mm (11.8 in) for degree of protection
IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and
IP54.
9)
The specified cabinet widths increase depending on the options selected.
For details, see description of options
L00
and
L01
.
© Siemens AG 2017