Technical specifications
(continued)
5
SINAMICS G120P Cabinet, converter cabinet units
SINAMICS G120P Cabinet, 75 kW to 630 kW
SINAMICS G120P Cabinet
Note:
The power data in hp units are based on the NEC/CEC stan-
dards for the North American market.
Information on the line connection, motor connection and
cabinet grounding can be found in section Cable cross-sections
and connections.
Line voltage 380 ... 480 V 3 AC
SINAMICS G120P Cabinet converter cabinet units
6SL3710-1PE31-5AB0-Z
6SL3710-1PE31-8AB0-Z
6SL3710-1PE32-1AB0-Z
6SL3710-1PE32-5AB0-Z
Rated power
• At
I
L
400 V/50 Hz
1)
kW
75
90
110
132
• At
I
L
460 V/60 Hz
2)
hp
75
100
125
150
• At
I
H
400 V/50 Hz
1)
kW
55
75
90
110
• At
I
H
460 V/60 Hz
2)
hp
60
75
100
125
Output current
• Rated current
I
rated
(400 V ±10 %)
A
145
178
205
250
• Rated current
I
rated
(480 V ±10 %)
A
120
148
170
207
• Base-load current
I
L
(400 V ±10 %)
3)
A
145
178
205
250
• Base-load current
I
L
(480 V ±10 %)
3)
A
120
148
170
207
• Base-load current
I
H
(400 V ±10 %)
4)
A
110
145
178
205
• Base-load current
I
H
(480 V ±10 %)
4)
A
91
120
148
170
• Output current, max.
A
196
241
277
338
Input current
• Rated current
I
rated
(400 V ±10 %)
5)
A
140
172
198
242
• Rated current
I
rated
(480 V ±10 %)
5)
A
117
143
165
202
• Base-load current
I
L
(400 V ±10 %)
3)
A
140
172
198
242
• Base-load current
I
L
(480 V ±10 %)
3)
A
117
143
165
202
• Base-load current
I
H
(400 V ±10 %)
4)
A
117
154
189
218
• Base-load current
I
H
(480 V ±10 %)
4)
A
97.5
128
157.5
182
• Input current, max.
A
189
232
267
327
Current requirement, 24 V DC
auxiliary power supply
6)
A
1
1
1
1
Short-circuit current rating
acc. to IEC
in conjunction with the specified fuses
without/with option L26
kA
65
65
65
65
Minimum short-circuit current
7)
• For 3NE1 fuses
A
1800
2400
3000
3000
• For 3NA3 fuses
A
4400
5000
7000
7000
Power loss, max.
at
I
rated
(400 V/40 °C), without options
kW
1.68
2.17
2.38
3.07
Coolant
Air
Air
Air
Air
Coolant requirements
m
3
/s
(ft
3
/s)
0.16 (5.65)
0.16 (5.65)
0.16 (5.65)
0.16 (5.65)
Sound pressure level
L
pA
(1 m)
at 50/60 Hz
dB
66/66
66/66
66/66
66/66
Cable length, max.
8)
between Power Module and motor
• When compliant with Categories C2
and C3 according to EN 61800-3
shielded
m (ft)
150 (492)
150 (492)
150 (492)
150 (492)
• When non-compliant with the limit
values for RI suppression and
without output reactor
unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
Dimensions
• Width
mm (in)
400 (15.75)
400 (15.75)
400 (15.75)
400 (15.75)
• Height
mm (in)
2000 (78.74)
2000 (78.74)
2000 (78.74)
2000 (78.74)
• Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
F
F
F
F
Weight
(degree of protection IP20, w/o options)
kg (lb)
165 (364)
165 (364)
165 (364)
165 (364)
1)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 400 V 3 AC/50 Hz
2)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 460 V 3 AC/60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
135 % for 3 s with a duty cycle duration of 300 s
(see overload capability
characteristics)
.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s with
a duty cycle duration of 300 s
(see overload capability characteristics)
.
5)
The current values given here are based on the rated output current.
6)
If the drive closed-loop control is still to remain active when the main line
supply fails, then the converter must be provided with an external 24 V DC
supply.
7)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
8)
Longer cable lengths are available on request.