SIEMENS
5/22
Siemens D 35 · 2017
■
Technical specifications
(continued)
5
SINAMICS G120P Cabinet, converter cabinet units
SINAMICS G120P Cabinet, 75 kW to 630 kW
SINAMICS G120P Cabinet
Deviations
from the specified classes are underlined
.
Ambient conditions
Storage
Transport
Operation
Ambient temperature
-25 ... +55 °C (-13 ... 131 °F)
-25 ... +70 °C (-13 ... 158 °F)
above -40 °C
(-40 °F) for 24 hours
0
... 40 °C (32 ... 104 °F)
up to 50 °C (122 °F)
see derating data
Relative humidity
(condensation not permissible)
5 ... 95 %
Class 1K4 acc. to EN 60721-3-1
5
... 95 %
Class 2K3 acc. to EN 60721-3-2
5 ... 95 %
Class 3K3 acc. to EN 60721-3-3
Environmental class/harmful
chemical substances
Class 1C2 acc. to EN 60721-3-1
Class 2C2 acc. to EN 60721-3-2
Class 3C2 acc. to EN 60721-3-3
Organic/biological influences
Class 1B1 acc. to EN 60721-3-1
Class 2B1 acc. to EN 60721-3-2
Class 3B1 according to EN 60721-3-3
Restriction: No conductive dust parti-
cles permitted
Degree of pollution
2 according to EN 61800-5-1
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating
> 1000 m (3281 ft)
see derating data
Mechanical strength
Storage
Transport
1)
Operation
Vibratory load
Class 1M2 acc. to EN 60721-3-1
Class 2M2 acc. to EN 60721-3-2
Class 3M2 acc. to EN 60721-3-3
• Deflection
1.5 mm at 5
... 9 Hz
3.5 mm at 2 ... 9 Hz
0.075 mm at 10 ... 58 Hz
• Acceleration
5 m/s
2
at > 9 ... 200 Hz
10 m/s
2
at > 9 ... 200 Hz
10 m/s
2
at > 58 ... 200 Hz
Shock load
Class 1M2 acc. to EN 60721-3-1
Class 2M2 acc. to EN 60721-3-2
Class 3M2 acc. to EN 60721-3-3
• Acceleration
40 m/s
2
at 22 ms
150 m/s
2
at 11 ms
50 m/s
2
(5 ×
g
)/30 ms
150 m/s
2
(15 ×
g
)/11 ms
Standards
Compliance with standards
cULus, CE, RCM, EAC, KC, SEMI F47
2)
CE marking
According to EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Machinery Directive 2006/42/EC
Radio interference suppression
The SINAMICS G120P Cabinet converter systems are not designed for connection to the public power network
("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed
drives EN 61800-3 "Second environment" (industrial line supplies). The equipment can cause electromagnetic inter-
ference when it is connected to the public network. However, if supplementary measures are taken (e.g. line filter,
see option
L00
) operation in the "first environment" is possible.
General technical specifications
1)
In transport packaging.
2)
SEMI F47 for frame size HX (500 V to 690 V) and frame size JX available
soon
© Siemens AG 2017