SIEMENS
4/87
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
dv/dt filters plus VPL
Line voltage 500 ... 690 V 3 AC
dv/dt filter plus VPL
6SL3000-2DH35-8AA0
6SL3000-2DH38-1AA0
1)
I
th max
A
575
810
Degree of protection
IP00
IP00
Cable length, max.
between dv/dt filter and motor
• Shielded
m (ft)
300 (984)
300 (984)
• Unshielded
m (ft)
450 (1476)
450 (1476)
Conformity
CE
CE
Certificates of suitability,
according to
cURus
cURus
dv/dt reactor
Power loss, max.
• At 50 Hz
kW
0.862
0.828
• At 60 Hz
kW
0.902
0.867
Connections
• To Power Module
2 × hole for M12
2 × hole for M12
• To load
2 × hole for M12
2 × hole for M12
• PE
M6 screw
M6 screw
Dimensions
• Width
mm (in)
460 (18.1)
445 (17.5)
• Height
mm (in)
385 (15.2)
385 (15.2)
• Depth
mm (in)
312 (12.3)
312 (12.3)
Weight, approx.
kg (lb)
172 (379)
160 (353)
Voltage Peak Limiter (VPL)
Power loss, max.
• At 50 Hz
kW
0.063
0.106
• At 60 Hz
kW
0.059
0.1
Connections
• To dv/dt reactor
1 x hole for M8
1 x hole for M10
• To DC link
1 x hole for M8
1 x hole for M10
• PE
M8 stud
M8 stud
Dimensions
• Width
mm (in)
309 (12.2)
309 (12.2)
• Height
mm (in)
1312.5 (51.7)
1312.5 (51.7)
• Depth
mm (in)
400 (15.7)
400 (15.7)
Weight, approx.
kg (lb)
48 (106)
72 (159)
Suitable for
PM330 Power Module
6SL3310-1PG33-7AA0
6SL3310-1PG34-0AA0
6SL3310-1PG34-5AA0
HX:
6SL3310-1PG35-2AA0
JX:
6SL3310-1PG35-8AA0
6SL3310-1PG36-5AA0
6SL3310-1PG37-2AA0
• Frame size
HX
HX/JX
1)
Two dv/dt reactors are required for these dv/dt filters. The listed technical
data refers to one
dv/dt reactor.
© Siemens AG 2017