SIEMENS
4/83
Siemens D 35 · 2017
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
Output reactors
■
Overview
Output reactor
Output reactors reduce the rate of voltage rise (
dv/dt
) and the
height of the current peaks, and enable longer motor cables to
be connected.
Owing to the high rates of voltage rise of the fast-switching
IGBTs, the capacitance of long motor cables reverses polarity
very quickly with every switching operation in the converter. As
a result, the motor is loaded with additional current peaks of sub-
stantial magnitude.
Output reactors reduce the magnitude of these additional peaks
because the cable capacitance reverses polarity more slowly
across the reactor inductance, thereby attenuating the ampli-
tudes of the current peaks.
When using output reactors, the following should be observed:
•
The output reactor must be installed as close as possible to
the Power Module.
■
Selection and ordering data
■
Technical specifications
Rated power
SINAMICS G120
PM330 Power Modules
Output reactor
400 V/
690 V
460 V/
575 V
kW
hp
Type 6SL3310-...
Frame size
Article No.
380 ... 480 V 3 AC
160
200
1PE33-0AA0
GX
6SL3000-2BE33-2AA0
200
250
1PE33-7AA0
GX
6SL3000-2BE33-8AA0
250
300
1PE34-6AA0
GX
6SL3000-2BE35-0AA0
315
400
1PE35-8AA0
HX
6SL3000-2AE36-1AA0
355
450
1PE36-6AA0
HX
6SL3000-2AE38-4AA0
400
500
1PE37-4AA0
450
500
1PE38-4AA0
JX
6SL3000-2AE41-0AA0
500
600
1PE38-8AA0
560
700
1PE41-0AA0
6SL3000-2AE41-4AA0
500 ... 690 V
3 AC
315
350
1PG33-7AA0
HX
6SL3000-2AH34-7AA0
355
400
1PG34-0AA0
400
450
1PG34-5AA0
HX
6SL3000-2AH35-8AA0
450
450
1PG35-2AA0
HX
6SL3000-2AH38-1AA0
500
500
1PG35-8AA0
JX
6SL3000-2AH38-1AA0
560
600
1PG36-5AA0
630
700
1PG37-2AA0
Line voltage 380 ... 480 V 3 AC
Output reactor
6SL3000-
2BE33-2AA0
6SL3000-
2BE33-8AA0
6SL3000-
2BE35-0AA0
6SL3000-
2AE36-1AA0
6SL3000-
2AE38-4AA0
Rated current
A
310
380
490
605
840
Power loss
kW
0.422
0.447
0.448
0.798
0.834
Connection
• To Power Module
1 × hole for M10
1 × hole for M10
1 × hole for M12
1 × hole for M12
1 × hole for M12
• To load
1 × hole for M10
1 × hole for M10
1 × hole for M12
1 × hole for M12
1 × hole for M12
• PE
M8 screw
M8 screw
M8 screw
M10 screw
M10 screw
Cable length, max.
between output reactor and motor
• Shielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
• Unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
Dimensions
• Width
mm (in)
300 (11.8)
300 (11.8)
300 (11.8)
410 (16.1)
410 (16.1)
• Height
mm (in)
285 (11.2)
285 (11.2)
365 (14.4)
392 (15.4)
392 (15.4)
• Depth
mm (in)
257 (10.1)
277 (10.9)
277 (10.9)
292 (11.5)
292 (11.5)
Degree of protection
IP00
IP00
IP00
IP00
IP00
Weight, approx.
kg (lb)
62 (137)
73 (161)
100 (220)
130 (287)
140 (309)
Suitable for
PM330 Power Module
Type
6SL3310-
1PE33-0AA0
6SL3310-
1PE33-7AA0
6SL3310-
1PE34-6AA0
6SL3310-
1PE35-8AA0
6SL3310-
1PE36-6AA0
6SL3310-
1PE37-4AA0
• Frame size
GX
GX
GX
HX
HX
© Siemens AG 2017