SIEMENS
4/79
Siemens D 35 · 2017
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
Recommended line-side power components
■
Selection and ordering data
The table below lists recommended ratings for input-end
switching and fuse protection elements for compliance with
IEC standards.
Notes
for use in compliance with IEC standards:
3NA3 or 3NE1 fuses are recommended for European countries.
Notes
for use in compliance with UL regulations:
UL-approved fuses must be used in North America.
Notes
regarding installations in Canada:
Overvoltage protection devices in accordance with overvoltage
category III and with the following ratings must be connected on
the line side of the converter:
•
Rated voltage 480 V/600 V (phase-phase), 480 V/600 V
(phase-to-ground) at a rated line voltage of 480 V/600 V
•
Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)
All overvoltage protection devices used must comply with
Canadian standards for industrial installations.
Additional information about the listed fuses can be found in
Catalogs LV 10, IC 10 and IC 10 AO.
Note:
Important! Note the minimum short-circuit current required to trip
the protection devices. If the minimum short-circuit current is not
reached, the tripping time of the fuses is increased, which can
lead to damage.
Rated
power
1)
SINAMICS G120
PM330
Power Modules
Main
contactor
acc. to
IEC
Switch
disconnector
acc. to IEC
Cable protection fuse
incl. semiconductor
protection
2)
acc. to IEC
Cable protection fuse
acc. to IEC
Cable protection
fuse
incl. semiconduc-
tor protection
acc. to UL/cUL
400 V/
690 V
460 V/
575 V
Type
Rated
current
Rated
current
Minimum
short-
circuit
current
Rated
current
Minimum
short-
circuit
current
Rated
current
kW
hp
6SL3310-...
Frame
size
Type
A
Type
A
A
Article No.
A
A
Article No.
A
Article No.
380 ... 480 V 3 AC
160
200
1PE33-0AA0
GX
3RT1456
2 units
400
3KL5730
450
3500
3NE1333-2
400
9500
3NA3260
450
3NE1333-2
200
250
1PE33-7AA0
GX
3RT1456
2 units
400
3KL5730
500
4500
3NE1334-2
500
14000
3NA3365
500
3NE1334-2
250
300
1PE34-6AA0
GX
3RT1456
3 units
630
3KL6130
560
7000
3NE1435-2
630
20000
3NA3372
560
3NE1435-2
315
400
1PE35-8AA0
HX
3RT1456
3 units
630
3KL6130
710
10000
3NE1437-2
710
3NE1437-2
355
450
1PE36-6AA0
HX
3RT1466
2 units
800
3KL6230
800
11000
3NE1438-2
800
30000
3NA3475
800
3NE1438-2
400
500
1PE37-4AA0
HX
3RT1466
3 units
800
3KL6230
850
13000
3NE1448-2
850
3NE1448-2
450
500
1PE38-4AA0
JX
3RT1466
3 units
1000
3KD5034
2 × 500
10400
3NE1334-3
2 units
1000
40000
3NA3480
1000
3NB3350-
1KK26
500
600
1PE38-8AA0
JX
3RT1466
3 units
1000
3KD5034
2 × 560
14000
3NE1435-3
2 units
1000
40000
3NA3480
1100
3NB3351-
1KK26
560
700
1PE41-0AA0
JX
3RT1476
2 units
1250
3KD5234
2 × 630
16000
3NE1436-3
2 units
1250
52000
3NA3482
1250
3NB3352-
1KK26
500 ... 690 V 3 AC
315
350
1PG33-7AA0 HX
3RT1476
400
3KL5730
450
3500
3NE1333-2
400
10000
3NA3360-6
450
3NE1333-2
355
400
1PG34-0AA0 HX
3RT1476
630
3KL6130
500
4500
3NE1334-2
425
10500
3NA3362-6
500
3NE1334-2
400
450
1PG34-5AA0 HX
3RT1476
630
3KL6130
560
7000
3NE1435-2
500
13000
3NA3365-6
560
3NE1435-2
450
450
1PG35-2AA0 HX
3RT1476
630
3KL6130
630
8500
3NE1436-2
2 x 315
14600
3NA3352-6
2 units
630
3NE1436-2
500
500
1PG35-8AA0 JX
3RT1466
3 units
630
3KD4634
710
10000
3NE1437-2
2 x 355
16000
3NA3354-6
2 units
710
3NE1437-2
560
600
1PG36-5AA0 JX
3RT1466
3 units
800
3KD4834
800
11000
3NE1438-2
2 x 400
20000
3NA3360-6
2 units
800
3NE1438-2
630
700
1PG37-2AA0 JX
3RT1466
3 units
1000
3KD5034
850
13000
3NE1448-2
2 x 425
21000
3NA3362-6
2 units
850
3NE1448-2
1)
Rated power based on the rated output current
I
rated
.
2)
Suitable for 3KL/3KD switch disconnector.
© Siemens AG 2017