SIEMENS
4/74
Siemens D 35 · 2017
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
Line filters
■
Overview
Line filter for Power Modules, frame size GX
To limit the emitted interference, the converters are equipped as
standard with a radio interference suppression filter that con-
forms to the limits defined in Category C3. Equipped with an
additional line filter, the PM330 Power Module also meet the
limits for use in the first environment (Category C2) as specified
in EN 61800-3
1)
.
The PM330 Power Modules comply with the immunity require-
ments defined in EN 61800-3 as standard for the second
environment.
In conjunction with line reactors, line filters also limit the con-
ducted interference emitted by the Power Modules to the limit
values of Category C2 defined in product standard EN 61800-3.
When combined with a plant design rigorously based on the
EMC installation guidelines, the limit values at the installation site
will conform to the requirements for the first environment.
The line filters are suitable for grounded systems
(TN or TT systems with grounded neutral point).
■
Selection and ordering data
Rated power
SINAMICS G120P, PM330
Power Modules
Line filter
in accordance with
EN 61800-3 Category C2
400 V/
690 V
460 V/
575 V
kW
hp
Type 6SL3310-...
Frame size
Article No.
380 ... 480 V
3 AC
160
200
1PE33-0AA0
GX
6SL3000-0BE33-1AA0
200
250
1PE33-7AA0
250
300
1PE34-6AA0
6SL3000-0BE35-0AA0
315
400
1PE35-8AA0
HX
6SL3760-0MR00-0AA0
355
450
1PE36-6AA0
400
500
1PE37-4AA0
450
500
1PE38-4AA0
JX
6SL3760-0MR00-0AA0
500
600
1PE38-8AA0
560
700
1PE41-0AA0
500 ... 690 V
3 AC
315
350
1PG33-7AA0
HX
6SL3760-0MS00-0AA0
355
400
1PG34-0AA0
400
450
1PG34-5AA0
450
450
1PG35-2AA0
500
500
1PG35-8AA0
JX
6SL3760-0MS00-0AA0
560
600
1PG36-5AA0
630
700
1PG37-2AA0
1)
Applies to shielded motor cable lengths of up to 150 m (492 ft).