Dimensional drawings
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
PM330 Power Modules
Principle dimension drawing and drill pattern for PM330 Power Modules, frame size HX
Secured with M8 bolts
Ventilation clearance required at the top: 200 mm
(7.87 in)
Ventilation clearance required at the bottom: 250 mm
(9.84 in)
Ventilation clearance required at sides: 30 mm
(1.18 in)
Ventilation clearance required at front: 100 mm
(3.94 in)
The PM330 Power Modules are designed for installation in a control cabinet.
All dimensions in mm
(values in brackets are in inches)
.
Lifting eyebolt
22.5
(0.89)
Mounting
surface
Rear view
G_D011_EN_00432
372.5
(14.67)
393
(15.47)
1659.6
(65.34)
255.2
(10.05)
218.6
(8.61)
9
(0.35)
9
(0.35)
9
(0.35)
Ø 20
(0.79)
Ø 30
(1.18)
274
(10.79)
49
(1.93)
25
(0.98)
21
(0.83)
199
(7.83)
1419
(55.87)
1695
(66.73)
509
(13.74)
39
(1.54)
349
(10.83)
499
(19.65)
548
(21.57)
© Siemens AG 2017