SIEMENS
4/66
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
PM330 Power Modules
Line supply connection
U1/L1, V1/L2, W1/L3
M12 screw
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
4 × 240
Motor connection
U2, V2, W2
M12 screw
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
4 × 240
DC link connection
DCP, DCN
M12 screw
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
4 × 240
PE/GND connection
M12 screw
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
(4+6) × 240
(4+6) × 240
(4+6) × 240
(4+6) × 240
Cable length, max.
between Power Module and motor
• When compliant with Categories C2
and C3 according to EN 61800-3
shielded
m (ft)
150 (492)
150 (492)
150 (492)
150 (492)
• When non-compliant with the limit
values for RI suppression and without
output reactor or dv/dt filter
unshielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
• When non-compliant with the limit
values for RI suppression with output
reactor or dv/dt filter
shielded/unshielded
m (ft)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
548 (21.6)
548 (21.6)
548 (21.6)
548 (21.6)
• Height
mm (in)
1695 (66.7)
1695 (66.7)
1695 (66.7)
1695 (66.7)
• Depth
mm (in)
393 (15.5)
393 (15.5)
393 (15.5)
393 (15.5)
Frame size
HX
HX
HX
HX
Weight, approx.
kg (lb)
158 (348)
158 (348)
162 (357)
162 (357)
Minimum size of control cabinet for
installation of a Power Module
• Width
mm (in)
800 (31.5)
800 (31.5)
800 (31.5)
800 (31.5)
• Height
mm (in)
2000 (78.7)
2000 (78.7)
2000 (78.7)
2000 (78.7)
• Depth
mm (in)
600 (23.6)
600 (23.6)
600 (23.6)
600 (23.6)
Line voltage 500 ... 690 V 3 AC
PM330 Power Modules
6SL3310-1PG33-7AA0
6SL3310-1PG34-0AA0
6SL3310-1PG34-5AA0
6SL3310-1PG35-2AA0
© Siemens AG 2017