Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
PM330 Power Modules
Line voltage 500 ... 690 V 3 AC
PM330 Power Modules
6SL3310-1PG33-7AA0
6SL3310-1PG34-0AA0
6SL3310-1PG34-5AA0
6SL3310-1PG35-2AA0
Rated power
1)
• Based on the base-load current
I
L
-
At 690 V/50 Hz
kW
315
355
400
450
-
At 575 V/60 Hz
hp
350
400
450
450
• Based on the base-load current
I
H
-
At 690 V/50 Hz
kW
250
315
355
400
-
At 575 V/60 Hz
hp
250
300
350
450
Output current
at 50 Hz 3 AC
• Rated current
I
rated
(500 V ±10 %)
A
368
400
453
516
• Rated current
I
rated
(600 V ±10 %)
A
353
396
441
497
• Rated current
I
rated
(690 V ±10 %)
A
340
393
430
480
• Base-load current
I
L
(500 V ±10 %)
2)
A
361
392
443
505
• Base-load current
I
L
(690 V ±10 %)
2)
A
330
385
420
470
• Base-load current
I
H
(500 V ±10 %)
3)
A
295
320
367
423
• Base-load current
I
H
(690 V ±10 %)
3)
A
272
314
348
394
• Max. output current
I
max
A
487
529
598
682
Rated pulse frequency
kHz
2
2
2
2
Input current
4)
• Rated current
I
rated
(500 V ±10 %)
A
383
416
471
537
• Rated current
I
rated
(600 V ±10 %)
A
367
412
459
517
• Rated current
I
rated
(690 V ±10 %)
A
354
409
447
499
• Base-load current
I
L
(500 V ±10 %)
2)
A
375
408
461
526
• Base-load current
I
L
(690 V ±10 %)
2)
A
343
401
437
489
• Base-load current
I
H
(500 V ±10 %)
3)
A
307
333
381
440
• Base-load current
I
H
(690 V ±10 %)
3)
A
283
327
362
410
• Max. input current
A
507
550
623
710
Short-circuit current rating
according to IEC
in conjunction with the specified fuses
kA
100
100
100
100
Rated short-circuit current SCCR
(Short-Circuit Current Rating)
in accordance with UL 61800-5-1
(up to 600 V)
in conjunction with the specified fuses
kA
100
100
100
100
Minimum short-circuit current
5)
• For 3NE1 fuses
A
3500
4500
7000
8500
Efficiency
η
at rated current
I
rated
(690 V/45 °C (113 °F))
%
98.2
98.2
98.2
98.2
Power loss
at rated current
I
rated
(690 V/45 °C (113 °F))
kW
5.402
6.191
6.884
7.716
Coolant requirements
m
3
/s (ft
3
/s)
0.362 (12.8)
0.362 (12.8)
0.362 (12.8)
0.362 (12.8)
Coolant
Air
Air
Air
Air
Sound pressure level
L
pA
(1 m)
dB
74
74
74
74
Power requirement 24 V DC supply
A
0.5
0.5
0.5
0.5
1)
Rated power of a typical 4-pole standard induction motor based on the
base-load current
I
L
or
I
H
at 690 V 3 AC/50 Hz (kW) or 575 V 3 AC/60 Hz
(hp).
2)
The base-load current
I
L
is based on the duty cycle for low overload (LO).
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
© Siemens AG 2017